Toshiba GR200 Series Instruction Manual page 692

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

◆ Connection point in PLC logic
SPOS01(Function ID: 510001)
Element ID
Name
800101EE65
SPOS01IN_TMP_40
810101EE66
SPOS01IN_TMP_41
810101EDDA
SPOS01IN_TMP_42
820101EE5E
SPOS01IN_TMP_44
830101EE5F
SPOS01IN_TMP_45
800101EE69
SPOS01IN_TMP_46
Mapping points in SPOS01
SPOS(FunctionID:510001)
Element ID
Name
7001016D08
DEV01_CONTROL_REQ
Note: In the table above, the user will only find Element IDs and their names for the 1
device, but a 2
have omitted the Element IDs and their names for the other devices to improve
readability. Use the rule described below when the user wishes to obtain the
Element IDs and their names for the other devices.
Rule: The same types of signal monitoring points are provided in every device;
hence, the user can find the same ones for all of the other devices. For
example, when the user wishes to find the "SPOS01_SC_OWS" point for
the 2
"SPOS02_SC_OWS". The user can obtain the ID value of
"SPOS02_SC_OWS" by using the following steps:
Description
SPOS01IN_TMP_40
SPOS01IN_TMP_41
SPOS01IN_TMP_42
SPOS01IN_TMP_44
SPOS01IN_TMP_45
SPOS01IN_TMP_46
Description
SPOS01 control command received. (Mapping Data)
and other devices are also provided in the SPOS function. We
nd
device, use the description of "SPOS01_SC_OWS" in place of
nd
Step 1
Find the element ID for SPOS01_SC_OWS (i.e.,
"8001011D51")
Step 2
Identify the number at the fifth digit from the ID. (i.e., "1")
Step 3
Choose a new device number. (i.e., pick the number "2" for
the 2
device)
nd
Step 4
Replace the number that occurs at the fifth digit with the
new device number. (i.e., get new ID "8001021D51" of
"SPOS02_SC_OWS") The ID is expressed in hexadecimal
notation. Thus, the user must change the device number
from decimal notation to hexadecimal notation.