Another OSTV element (OSTV-2) is provided when the protection is carried out by three
IEDs. The characteristic of the OSTV-2 element is the same as the characteristic of the OSTV-
1 element.
Note that to detect the state of out-of-step, phasor V B should stay at each quadrant for
the setting time (1.5 cycles). This is because that the influence of any VT transient should be
cancelled. The voltages in positive-sequence are used for the calculation of the OSTV function;
and when amplitudes are larger than 1V, the operation of the OSTV function is valid.
Figure 2.27-3 Voltage phase comparison between terminal A and terminal C (OSTV-2)
-zone
V C
-zone
- 352 -
1V
V A
6F2S1914 (0.49)