When VCHK1 and VCHK2 are used in 1.5CB system, set the scheme switches [SYN-
VBus], [SYN-VLine], and [SYN-VLine2]. For example, the settings in Figure 2.35-9 are applied
when VCHK 1 and VCHK2 are applied in the 1.5CB system.
Table 2.35-10 Setting example for 1.5CB system
Output voltage
at VT
Input
voltage
at VCT
VCHK Setting
3
Note: Set V-L2 for the scheme switch [SYN-VLine]. This is because V3 and V L2 are in
3
the same phase. Set V4 for the scheme switch [SYN-VLine2]. This is because V3
and V4 are in the same phase.
Table 2.35-11 VCHK line1 and line2 selection setting
Scheme switch
Set
V-L1 / V-L2 / V-L3 / V-L12 / V-L23 /
SYN-VBus
V-L31 / V2-L1 / V2-L2 / V2-L3 / V2-
V-L1 / V-L2 / V-L3 / V-L12 / V-L23 /
SYN-VLine
V-L31 / V2-L1 / V2-L2 / V2-L3 / V2-
V-L1 / V-L2 / V-L3 / V-L12 / V-L23 /
SYN-VLine2
V-L31 / V2-L1 / V2-L2 / V2-L3 / V2-
Bus-bar VT=
Phase-B
Line VT=
Three phase
Line2 VT=
Phase-B
Running voltage of SYN1(V S )=Phase-B (Bus-bar VT)
Incoming voltage of SYN1 and SYN2 (V b )=Phase-B (Line VT)
Running voltage of SYN2 (V S2 )= Phase-B (Line2 VT)
[SYN-VBus] =
V3
[SYN-VLine]=
V-L2
[SYN-VLine2] = V4
L12 / V2-L23 / V2-L31 / V3 / V4
L12 / V2-L23 / V2-L31 / V3 / V4
L12 / V2-L23 / V2-L31 / V3 / V4
- 488 -
6F2S1914 (0.49)
Comment
Selection of Bus
voltage(Running Voltage) for
SYN1
Selection of Line voltage
(Incoming Voltage) for SYN1
and SYN2
Selection of Line2 voltage
(Running voltage) for SYN2
GRL200 (Soft 033 & 037)