SPAR and TPAR mode
(iii)
Figure 2.34-4 illustrates the ARC function when settings of are performed in both Table 2.34-7
and Table 2.34-8.
Table 2.34-7 Block parts in SPAR and TPAR mode
Block parts
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]
[11]
Table 2.34-8 Setting examples in SPAR and TPAR mode
Categories
ARC general
Multi Shot-EN
ARC1
TTPAR1_SUB
ARC1 multi-shot
ARC misc.
SHOTNUM-TEST
PROT-COMMON
VCHK
ARC1-VCHK EN
TRC
Corresponding logics
ARC1-Mode input
Shot number
Start
Initiation
Shot counter
Condition
ARC1 TPAR
ARC1 SHOT2
Issuing
Success check
Reclose sequence
Items
Settings
ARC1-EN
ARC1-Mode
SPAR&TPAR
ARC2-EN
ARC2-Mode
ARC-ORDER
ARC-NUM
TREADY
TSPAR1
TSPAR1_SUB
300.00s
TTPAR1
300.00s
TRR1
TCCW1
TD_MS2
TRR_MS2
ARC-SucChk
TARCSUC
FT-3pFault
TRESET
TEVLV
CB-System
TP-MODE
Per-Phase
- 436 -
Detailed logic
Figure 2.34-11
Figure 2.34-13
Figure 2.34-14
Figure 2.34-15
Figure 2.34-16
Figure 2.34-17
Figure 2.34-20
Figure 2.34-21
Figure 2.34-22
Figure 2.34-23
Figure 2.34-24
Corresponding logics
On
Figure 2.34-11
Off
Off
Figure 2.34-12
CB1
Figure 2.34-24
On
S2
Figure 2.34-13
60.0s
Figure 2.34-15
0.80s
Figure 2.34-18
Figure 2.34-18
0.60s
Figure 2.34-20
Figure 2.34-20
2.00s
Figure 2.34-20
0.20s
Figure 2.34-22
20.00s
Figure 2.34-21
30.00s
Figure 2.34-21
On
Figure 2.34-23
0.30s
Figure 2.34-23
Off
Figure 2.34-14
0.30s
Figure 2.34-15
0.30s
Figure 2.34-17
Off
Figure 2.34-16
1CB
See Protection common function
On
See Voltage check for autoreclose
See Trip circuit