Toshiba GR200 Series Instruction Manual page 398

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

8000001C23
EFCTF
8100001C27
OVGCTF
On
≥1
CTF-EN
OPT-On
&
1
From PROT-CCOMMON
1
CB_ALLPH_CLOSE
0.02s
From DISTANSE-ZS
2
PSBS-VCTF-BLK
From DISTANSE-ZG
2
PSBG-VCTF-BLK
From test
4
AMF_OFF
1
800000EBB0
CTF_BLOCK
810000EBB1
EXTERNAL_CTF
Figure 2.31-1 Scheme logic in the CTF function
Note: Signal CB_ALLPH_CLOSE is provided from Protection common function
1
(PROT_COMMON). For more information, see Chapter
Protection common
Note: Entering signals come from distance protections (ZS/ZG) when the ZS/ZG are
2
available in the IED. For more information, see Chapter
Distance protection
Note: Output signals are provided for respective relays when the relays are available.
3
Appendix: Ordering
See
Note: AMF feature is used for the test. To generate the AMF signal, see chapter
4
interface: test-submenu
If a PLC signal is injected at the PLC connection point "CTF_BLOCK", the operation of
the CTF function is blocked. The user can program to inject an external signal for the failure
detection using the PLC connection point EXTERNAL_CTF; the CTF_DETECT signal is
generated when the signal is injected at the EXTERNAL_CTF.
&
1
t
0
0.015s
&
1
≥1
1
8100001BB1
.
.
whether the relays are supplied into the IED.
.
- 375 -
8100001B60
≥1
S
t
0
≥1
R
1
0.1s
Relay application:
Relay application:
6F2S1914 (0.49)
8000001B61
t
0
CTF_ALARM
To Automatic supervision
10.0s
To EF
3
To BCD
3
To OCN
3
8000001B62
≥1
CTF_DETECT
User
GRL200 (Soft 033 & 037)