Toshiba GR200 Series Instruction Manual page 687

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Object_reference
Ctrl/GGIO1501$SPCSO$origin
Ctrl/GGIO1501$SPCSO$origin
Ctrl/GGIO1501$SPCSO
Ctrl/GGIO1501$SPCSO
Ctrl/GGIO1501$SPCSO
Ctrl/GGIO1501$SPCSO
Note: "Status (ST)" is defined in the function constraint (FC) of the IEC 61850 standard.
Figure 4.1-43 ocCat attribute mapped for SPCSO object of GGIO1501
Mapping input data
(iii)
The SPOS01 function can receive three commands "select, operate, and cancel". Thus, the user
should map the input-point " DEV01_CONTROL_REQ" to the IEC 61850 communication. Table
4.1-31
shows
"Ctrl/GGIO1501$SPCSO" ; the user should map the input point to the Object reference having
attributes CO and CF†. Figure 4.1-44 shows how to map a signal.
Table 4.1-30 Mapping signals for SPCSO object
Attribute
Type
orCat
orCategory
orIdent
Octet64
stVal
BOOLEAN
q
Quality
t
Timestamp
stSeld
BOOLEAN
the
input-point
"DEV01_CONTROL_REQ"
- 664 -
FC
Signal Number
ST
510001 3001011008
ST
510001 6A01011009
ST
510001 0001011001
ST
510001 3101011005
ST
510001 9001011006
ST
510001 0001011D90
Drag and drop
and
6F2S1914 (0.49)
Signal Name
SPOS01_ORCAT
SPOS01_ORIDENT
SPOS01_STATE
SPOS01_QUALITY
SPOS01_TIMESTAMP
SPOS01_STD_RPT
the
Object
reference
GRL200 (Soft 033 & 037)

Advertisement

Table of Contents
loading

Table of Contents