Scalar Control; Settings; Ir Compensation For A Scalar Controlled Drive; Programmable Protection Functions - ABB ACS350 User Manual

Hide thumbs Also See for ACS350:
Table of Contents

Advertisement

Scalar control

It is possible to select scalar control as the motor control method instead of vector
control. In the scalar control mode, the drive is controlled with a frequency reference.
It is recommended to activate the scalar control mode in the following special
applications:
• In multimotor drives: 1) if the load is not equally shared between the motors,
2) if the motors are of different sizes, or 3) if the motors are going to be changed
after the motor identification.
• If the nominal current of the motor is less than 20% of the nominal output current
of the drive.
In the scalar control mode, some standard features are not available.

Settings

Parameter

IR compensation for a scalar controlled drive

IR compensation is active only when the motor
control mode is scalar (see section
on page 115). When IR compensation is
activated, the drive gives an extra voltage boost
to the motor at low speeds. IR compensation is
useful in applications that require high breakaway
torque. In vector control, no IR compensation is
possible/needed.
Settings
Parameter

Programmable protection functions

AI<Min
AI<Min function defines the drive operation if an analog input signal falls below the
set minimum limit.
Settings
Parameters
LIMIT

Panel Loss

Panel Loss function defines the operation of the drive if the control panel selected as
control location for the drive stops communicating.
Settings
Parameter
9904
MOTOR CTRL MODE
2603
IR COMP VOLT
3001
AI<MIN FUNCTION,
3002
PANEL COMM ERR
Motor voltage
Scalar control
IR compensation
3021
AI1 FAULT LIMIT and
115
No compensation
f (Hz)
3022
AI2 FAULT
Program features

Advertisement

Table of Contents
loading

Table of Contents