Maintenance and hardware diagnostics

What this chapter contains

The chapter contains preventive maintenance instructions and LED indicator
descriptions.

Safety

WARNING! Read the instructions in chapter
before performing any maintenance on the equipment. Ignoring the safety
instructions can cause injury or death.

Maintenance intervals

If installed in an appropriate environment, the drive requires very little maintenance.
The table lists the routine maintenance intervals recommended by ABB.
Reforming of capacitors
Cooling fan replacement
(frame sizes R1...R4)
Replacement of the battery in
the Assistant Control Panel

Fan

The drive's cooling fan has a life span of minimum 25 000 operating hours. The
actual life span depends on the drive usage and ambient temperature.
When the Assistant Control Panel is in use, the Notice Handler Assistant informs
when the definable value of the operating hour counter is reached (see parameter
2901). This information can also be passed to the relay output (see parameter 1401)
regardless of the used panel type.
Fan failure can be predicted by the increasing noise from the fan bearings. If the
drive is operated in a critical part of a process, fan replacement is recommended
once these symptoms start appearing. Replacement fans are available from ABB.
Do not use other than ABB specified spare parts.
Maintenance
Every two years when stored
Every three years
Every ten years
Safety
on the first pages of this manual
Interval
See
See
See
Maintenance and hardware diagnostics
285
Instruction
Capacitors
on page 286.
Fan
on page 285.
Battery
on page 287.