Apply input power and wait for a moment.
Check that the red LED is not lit and the green LED is lit but not blinking.

How to perform the limited start-up

For the limited start-up, you can use the Basic Control Panel or the Assistant Control
Panel. The instructions below are valid for both control panels, but the displays
shown are the Basic Control Panel displays, unless the instruction applies to the
Assistant Control Panel only.
Before you start, ensure that you have the motor nameplate data on hand.
The start-up may only be carried out by a qualified electrician.
The safety instructions given in chapter
procedure.
The drive will start up automatically at power up if the external run command is on.
Check the installation. See the checklist in chapter
Check that the starting of the motor does not cause any danger.
De-couple the driven machine if:
• there is a risk of damage in case of incorrect direction of rotation, or
• an ID Run needs to be performed during the drive start-up. ID Run is essential only in
applications that require the ultimate in motor control accuracy.
Apply input power.
The Basic Control Panel powers up into the Output mode.
The Assistant Control Panel asks if you want to run the Start-
up Assistant. If you press
run, and you can continue with manual start-up in a similar
manner as described below for the Basic Control Panel.
Start-up, control with I/O and ID Run
POWER-UP
The drive is now ready for use.
SAFETY
Safety
POWER-UP
EXIT
, the Start-up Assistant is not
must be followed during the start-up
Installation
checklist.