Parameters – complete descriptions
Index Name/Selection
3623
BOOSTER TIME
00:00:00...23:59:58
3626
TIMED FUNC 1 SRC
NOT SEL
T1
T2
T1+T2
T3
T1+T3
T2+T3
T1+T2+T3
T4
T1+T4
T2+T4
T1+T2+T4
T3+T4
T1+T3+T4
T2+T3+T4
T1+T2+T3+T4
BOOSTER
T1+B
T2+B
T1+T2+B
T3+B
T1+T3+B
T2+T3+B
T1+T2+T3+B
T4+B
T1+T4+B
T2+T4+B
T1+T2+T4+B
Description
Defines the time inside which the booster is deactivated after the booster
activation signal is switched off.
hours:minutes:seconds
Example: If parameter 3622 BOOSTER SEL is set to DI1 and 3623
BOOSTER TIME is set to 01:30:00, the booster is active for 1 hour and 30
minutes after digital input DI is deactivated.
Booster active
DI
Selects the time periods for TIMED FUNC 1 SCR. Timed function can
consists of 0...4 time periods and a booster.
No time periods selected
Time period 1
Time period 2
Time periods 1 and 2
Time period 3
Time periods 1 and 3
Time periods 2 and 3
Time periods 1, 2 and 3
Time period 4
Time periods 1 and 4
Time periods 2 and 4
Time periods 1, 2 and 4
Time periods 4 and 3
Time periods 1, 3 and 4
Time periods 2, 3 and 4
Time periods 1, 2, 3 and 4
Booster
Booster and time period 1
Booster and time period 2
Booster and time periods 1 and 2
Booster and time period 3
Booster and time periods 1 and 3
Booster and time periods 2 and 3
Booster and time periods 1, 2 and 3
Booster and time period 4
Booster and time periods 1 and 4
Booster and time periods 2 and 4
Booster and time periods 1, 2 and 4
Booster time
Actual signals and parameters
213
Def, FbEq
00:00:00
NOT SEL
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27

Advertisement

Table of Contents
loading

Table of Contents