Parameters – complete descriptions
Index Name/Selection
1209
TIMED MODE SEL
EXT/CS1/2/3
CS1/2/3/4

13 ANALOGUE INPUTS

1301
MINIMUM AI1
-100.0...100.0%
1302
MAXIMUM AI1
-100.0...100.0%
Description
Selects timed function activated speed into use when parameter
CONST SPEED SEL selection is TIMED FUN1&2.
External speed reference or constant speed selection with TIMED FUNC 1
and TIMED FUNC 2. 1 = timed function active, 0 = timed function inactive.
TIMED
TIMED
Operation
FUNC 1
FUNC 2
0
0
External reference
1
0
Speed defined by parameter
0
1
Speed defined by parameter
1
1
Speed defined by parameter
Constant speed selection with TIMED FUNC 1 and TIMED FUNC 2.
1 = timed function active, 0 = timed function inactive.
TIMED
TIMED
Operation
FUNC 1
FUNC 2
0
0
Speed defined by parameter
1
0
Speed defined by parameter
0
1
Speed defined by parameter
1
1
Speed defined by parameter
Analog input signal processing
Defines the minimum %-value that corresponds to minimum mA/(V) signal for
analog input AI1. When used as a reference, the value corresponds to the
reference minimum setting.
0...20 mA
=
0...100%
4...20 mA
=
20...100%
-10...10 mA
=
-50...50%
Example: If AI1 is selected as the source for external reference REF1, this
value corresponds to the value of parameter
Note: MINIMUM AI value must not exceed MAXIMUM AI value.
Value in percent of the full signal range. Example: If the minimum value for
analog input is 4 mA, the percent value for 0...20 mA range is:
(4 mA / 20 mA) · 100% = 20%
Defines the maximum %-value that corresponds to maximum mA/(V) signal
for analog input AI1. When used as a reference, the value corresponds to the
reference maximum setting.
0...20 mA
=
0...100%
4...20 mA
=
20...100%
=
-10...10 mA
-50...50%
Example: If AI1 is selected as the source for external reference REF1, this
value corresponds to the value of parameter
Value in percent of the full signal range. Example: If the maximum value for
analog input is 10 mA, the percent value for 0...20 mA range is:
(10 mA / 20 mA) · 100% = 50%
1201
1202
CONST SPEED 1
1203
CONST SPEED 2
1204
CONST SPEED 3
1202
CONST SPEED 1
1203
CONST SPEED 2
1204
CONST SPEED 3
1205
CONST SPEED 4
1104
REF1 MIN.
1105
REF1 MAX.
Actual signals and parameters
167
Def, FbEq
CS1/2/3/4
1
2
1%
1 = 0.1%
100
1 = 0.1%

Advertisement