ABB ACS350 User Manual page 202

Hide thumbs Also See for ACS350:
Table of Contents

Advertisement

202
Parameters – complete descriptions
Index Name/Selection
3103
DELAY TIME
0.0...120.0 s
3104
AR OVERCURRENT
DISABLE
ENABLE
3105
AR OVERVOLTAGE
DISABLE
ENABLE
3106
AR UNDERVOLTAGE
DISABLE
ENABLE
3107
AR AI<MIN
DISABLE
ENABLE
3108
AR EXTERNAL FLT
DISABLE
ENABLE
Actual signals and parameters
Description
Defines the time that the drive will wait after a fault before attempting an
automatic reset. See parameter
zero, the drive resets immediately.
Time
Activates/deactivates the automatic reset for the overcurrent fault.
Automatically resets the fault (OVERCURRENT) after the delay set by par.
3103
DELAY TIME.
Inactive
Active
Activates/deactivates the automatic reset for the intermediate link
overvoltage fault. Automatically resets the fault (DC OVERVOLT) after the
delay set by par.
3103
DELAY TIME.
Inactive
Active
Activates/deactivates the automatic reset for the intermediate link
undervoltage fault. Automatically resets the fault (DC UNDERVOLTAGE)
after the delay set by par.
Inactive
Active
Activates/deactivates the automatic reset for fault AI<MIN (analog input
signal under the allowed minimum level). Automatically resets the fault after
the delay set by par.
3103
Inactive
Active
WARNING! The drive may restart even after a long stop if the
analog input signal is restored. Ensure that the use of this feature
will not cause danger.
Activates/deactivates the automatic reset for the EXTERNAL FAULT 1/2.
Automatically resets the fault after the delay set by par.
Inactive
Active
3101
NR OF TRIALS. If delay time is set to
3103
DELAY TIME.
DELAY TIME.
Def, FbEq
0
1 = 0.1 s
DISABLE
0
1
DISABLE
0
1
DISABLE
0
1
DISABLE
0
1
DISABLE
3103
DELAY TIME.
0
1