Example 1

50 Hz
0 Hz
-50 Hz
DI1
DI2
Sequence programming is activated by digital input DI1.
ST1: Drive is started in reverse direction with -50 Hz reference and 10 s ramp time.
State 1 is active for 40 s.
ST2: Drive is accelerated to 20 Hz with 60 s ramp time. State 2 is active for 120 s.
ST3: Drive is accelerated to 25 Hz with 5 s ramp time. State 3 is active until the
sequence programming is disabled or until booster start is activated by DI2.
ST4: Drive is accelerated to 50 Hz with 5 s ramp time. State 4 is active for 200 s and
after that the state shifts back to state 3.
Parameter
1002
EXT2 COMMANDS
1102
EXT1/EXT2 SEL
1106
REF2 SELECT
1601
RUN ENABLE
2102
STOP FUNCTION
2201
ACC/DEC 1/2 SEL
8401
SEQ PROG ENABLE
8402
SEQ PROG START
8404
SEQ PROG RESET
ST1
Par.
Setting
8420
ST1 REF SEL
100%
8421
ST1
START
COMMANDS
REV
8422
ST1 RAMP
10 s
8424
ST1 CHANGE
40 s
DLY
8425
ST1 TRIG TO
CHANGE
ST 2
DLY
8426
ST1 TRIG TO
NOT SEL
ST N
8427
ST1 STATE N
-
Program features
ST1
ST2
Seq. start
Setting
Additional information
SEQ PROG
Start, stop, direction commands for EXT2
EXT2
EXT2 activation
SEQ PROG
Sequence programming output as REF2
NOT SEL
Deactivation of Run Enable
RAMP
Ramp stop
SEQ PROG
Ramp as defined by parameter 8422/.../8452.
ALWAYS
Sequence programming enabled
DI1
Sequence programming activation through digital input (DI1)
DI1(INV)
Sequence programming reset (i.e. reset to state 1, when DI1 signal is
lost (1 -> 0)
ST2
Par. Setting
8430 40%
8431 START
FRW
8432 60 s
8434 120 s
8435 CHANGE
DLY
8436 NOT SEL
8437 -
ST3
State change trigger
ST3
Par.
Setting
Par.
8440 50%
8450 100%
8441 START
8451 START
FRW
8442 5 s
8452 5 s
8444
8454 200 s
8445 DI2
8455
8446 NOT SEL
8456 CHANGE
8447 -
8457 3
ST4
ST3
ST4
Additional
information
Setting
State reference
Run, direction and stop
FRW
command
Ramp time
State change delay
State change trigger
DLY