Pid Control Macro; Default I/O Connections - ABB ACS350 User Manual

Hide thumbs Also See for ACS350:
Table of Contents

Advertisement

92

PID Control macro

This macro provides parameter settings for closed-loop control systems such as
pressure control, flow control, etc. Control can also be switched to speed control
using a digital input. To enable the macro, set the value of parameter
CONTROL).
For the parameter default values, see section
on page 142. If you use other than the default connections presented below, see
section
Note: Parameter

Default I/O connections

1...10 kohm
max. 500 ohm
1)
Hand: 0...10 V -> speed reference.
PID:
2)
360 degree grounding under a clamp.
Application macros
I/O terminals
on page 40.
2108
START INHIBIT must remain in the default setting 0 (OFF).
X1A
1
SCR
2
AI1
3
GND
4
+10V
5
AI2
6
GND
7
AO
8
GND
2)
9
+24V
10
GND
11
DCOM
12
DI1
13
DI2
14
DI3
15
DI4
16
DI5
X1B
17
ROCOM
18
RONC
19
RONO
20
DOSRC
21
DOOUT
22
DOGND
0...10 V -> 0...100% PID setpoint.
Default values with different macros
Signal cable shield (screen)
Motor speed ref. (Hand) / Process ref. (PID): 0...10 V
Analog input circuit common
Reference voltage: +10 VDC, max. 10 mA
Process actual value: 4...20 mA
Analog input circuit common
Motor speed value: 0...20 mA
Analog output circuit common
Auxiliary voltage output: +24 VDC, max. 200 mA
Auxiliary voltage output common
Digital input common
Stop (0) / Start (1) (Hand)
Hand (0) / PID (1) control selection
Constant speed 1: parameter
Run enable
Stop (0) / Start (1) (PID)
Relay output
No fault [Fault (-1)]
Digital output, max. 100 mA
No fault [Fault (-1)]
3)
The signal source must be powered externally.
See the manufacturer's instructions. An
example of a connection using a two-wire
sensor is given on page 41.
Tightening torque = 0.5 N·m / 4.4 lbf. in.
9902
to 6 (PID
1)
3)
1202

Advertisement

Table of Contents
loading

Table of Contents