ABB ACS350 User Manual page 149

Hide thumbs Also See for ACS350:
Table of Contents

Advertisement

Parameters – short form list
Index
Name/Selection
1502
AO1 CONTENT MIN
1503
AO1 CONTENT MAX
1504
MINIMUM AO1
1505
MAXIMUM AO1
1506
FILTER AO1
16
SYSTEM CONTROLS
1601
RUN ENABLE
1602
PARAMETER LOCK
1603
PASS CODE
1604
FAULT RESET SEL
1605
USER PAR SET CHG
1606
LOCAL LOCK
1607
PARAM SAVE
1608
START ENABLE 1
1609
START ENABLE 2
1610
DISPLAY ALARMS
1611
PARAMETER VIEW
18
FREQ IN & TRAN OUT Frequency input and transistor output signal processing.
1801
FREQ INPUT MIN
1802
FREQ INPUT MAX
1803
FILTER FREQ IN
1804
TO MODE
1805
DO SIGNAL
1806
DO ON DELAY
1807
DO OFF DELAY
1808
FO CONTENT SEL
1809
FO CONTENT MIN
1810
FO CONTENT MAX
1811
MINIMUM FO
1812
MAXIMUM FO
1813
FILTER FO
19
TIMER & COUNTER
1901
TIMER DELAY
1902
TIMER START
1903
TIMER RESET
1904
COUNTER ENABLE
1905
COUNTER LIMIT
1906
COUNTER INPUT
1907
COUNTER RESET
1908
COUNTER RES VAL
1909
COUNT DIVIDER
1910
COUNT DIRECTION
1911
CNTR S/S COMMAND Selects the source for the drive start/stop command when
Description
Defines the minimum value for signal selected with parameter
1501 AO1 CONTENT SEL.
Defines the maximum value for signal selected with parameter
1501 AO1 CONTENT SEL.
Defines the minimum value for the analog output signal AO.
Defines the maximum value for the analog output signal AO.
Defines the filter time constant for analog output AO, i.e the time
within 63% of a step change is reached.
Run Enable, parameter lock etc.
Selects a source for the external Run Enable signal.
Selects the state of the parameter lock.
Selects the pass code for the parameter lock.
Selects the source for the fault reset signal.
Enables the change of the User Parameter Set through a digital
input.
Disables entering local control mode or selects the source for the
local control mode lock signal.
Saves the valid parameter values to the permanent memory.
Selects the source for the Start Enable 1 signal.
Selects the source for the Start Enable 2 signal.
Activates/deactivates alarms.
Selects the parameter view, i.e which parameters are shown.
Defines the minimum input value when DI5 is used as a
frequency input.
Defines the maximum input value when DI5 is used as a
frequency input.
Defines the filter time constant for frequency input.
Selects the operation mode for the transistor output TO.
Selects a drive status indicated through digital output DO.
Defines the operation delay for digital output DO.
Defines the release delay for digital output DO.
Selects a drive signal to be connected to frequency output FO.
Defines the minimum frequency output FO signal value.
Defines the maximum frequency output FO signal value.
Defines the minimum value for frequency output FO.
Defines the maximum value for frequency output FO.
Defines the filter time constant for frequency output FO.
Timer and counter for start and stop control
Defines the time delay for the timer.
Selects the source for the timer start signal.
Selects the source for the timer reset signal.
Selects the source for the counter enable signal.
Defines the counter limit.
Selects the input signal source for the counter.
Selects the source for the counter reset signal.
Defines the value for the counter after reset.
Defines the divider for the pulse counter.
Defines the source for the counter direction selection.
parameter 1001 EXT1 COMMANDS value is set to COUNTER
START / COUNTER STOP.
Def
Custom
-
-
0
20
0.1
NOT SEL
OPEN
0
KEYPAD
NOT SEL
NOT SEL
DONE
NOT SEL
NOT SEL
NO
DEFAULT
0
1000
0.1
DIGITAL
FAULT(-1)
0
0
104
-
-
10
1000
0.1
10
NOT SEL
NOT SEL
DISABLED
1000
PLS IN(DI5)
NOT SEL
0
0
UP
NOT SEL
Actual signals and parameters
149