ABB ACS350 User Manual page 160

Hide thumbs Also See for ACS350:
Table of Contents

Advertisement

160
Parameters – complete descriptions
Index Name/Selection
DI5,4
TIMER STOP
TIMER START
COUNTER STOP
COUNTER START
SEQ PROG
1002
EXT2 COMMANDS
1003
DIRECTION
FORWARD
REVERSE
REQUEST
1010
JOGGING SEL
DI1
DI2
DI3
DI4
DI5
COMM
NOT SEL
DI1(INV)
DI2(INV)
DI3(INV)
DI4(INV)
DI5(INV)
Actual signals and parameters
Description
Start and stop through digital input DI5. 0 = stop, 1 = start. Direction through
digital input DI4. 0 = forward, 1 = reverse. To control direction, parameter
1003
DIRECTION must be REQUEST.
Stop when timer delay defined by parameter
passed. Start with timer start signal. Source for the signal is selected by
parameter
1902
TIMER START.
Start when timer delay defined by parameter
passed. Stop when timer is reset by parameter
Stop when counter limit defined by parameter
been exceeded. Start with counter start signal. Source for the signal is
selected by parameter
1911
Start when counter limit defined by parameter
been exceeded. Stop with counter stop signal. Source for the signal is
selected by parameter
1911
Start, stop and direction commands through sequence programming. See
parameter group
84 SEQUENCE
Defines the connections and the source for the start, stop and direction
commands for external control location 2 (EXT2).
See parameter
1001
EXT1 COMMANDS.
Enables the control of rotation direction of the motor, or fixes the direction.
Fixed to forward
Fixed to reverse
Direction of rotation control allowed
Defines the signal that activates the jogging function. See section
page 129.
Digital input DI1. 0 = jogging inactive, 1 = jogging active.
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1.
Fieldbus interface as the source for jogging 1 or 2 activation, i.e. control word
0302
FB CMD WORD 2 bits 20 and 21. The control word is sent by the
fieldbus controller via the fieldbus adapter or embedded fieldbus (modbus) to
the drive. For the control word bits, see section
on page 262.
Not selected
Inverted digital input DI1. 1 = jogging inactive, 0 = jogging active.
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
1901
TIMER DELAY has
1901
TIMER DELAY has
1903
TIMER RESET.
1905
COUNTER LIMIT has
CNTR S/S COMMAND.
1905
COUNTER LIMIT has
CNTR S/S COMMAND.
PROG.
DCU communication profile
Def, FbEq
21
22
23
24
25
26
NOT SEL
REQUEST
1
2
3
Jogging
on
NOT SEL
1
2
3
4
5
6
0
-1
-2
-3
-4
-5