ABB ACS350 User Manual page 265

Hide thumbs Also See for ACS350:
Table of Contents

Advertisement

Bit
Name
16
ALARM
17
NOTICE
18
DIRLOCK
19
LOCALLOCK
20
CTL_MODE
21
JOGGING ACTIVE
22...25
Reserved
26
REQ_CTL
27
REQ_REF1
28
REQ_REF2
29
REQ_REF2EXT
30
ACK_STARTINH
31
Reserved
DCU Profile Status Word (par. 0304)
Value
1
An alarm is on.
0
No alarms are on.
1
A maintenance request is pending.
0
No maintenance request
1
Direction lock is ON. (Direction change is locked.)
0
Direction lock is OFF.
1
Local mode lock is ON. (Local mode is locked.)
0
Local mode lock is OFF.
1
Drive is in vector control mode.
0
Drive is in scalar control mode.
Jogging function is active.
1
Control Word requested from fieldbus
0
No operation
1
Reference 1 requested from fieldbus
0
Reference 1 is not requested from fieldbus.
1
Reference 2 requested from fieldbus
0
Reference 2 is not requested from fieldbus.
1
External PID reference 2 requested from fieldbus
0
External PID reference 2 is not requested from fieldbus.
1
Start inhibit from fieldbus
0
No start inhibit from fieldbus
Status
Fieldbus control with embedded fieldbus
265

Advertisement

Table of Contents
loading