31 Automatic Reset - ABB ACS350 User Manual

Hide thumbs Also See for ACS350:
Table of Contents

Advertisement

Parameters – complete descriptions
Index Name/Selection
LAST SPEED
3019
COMM FAULT TIME
0.0...60.0 s
3021
AI1 FAULT LIMIT
0.0...100.0%
3022
AI2 FAULT LIMIT
0.0...100.0%
3023
WIRING FAULT
DISABLE
ENABLE

31 AUTOMATIC RESET

3101
NR OF TRIALS
0...5
3102
TRIAL TIME
1.0...600.0 s
Description
Protection is active. The drive generates alarm IO COMM and freezes the
speed to the level the drive was operating at. The speed is determined by the
average speed over the previous 10 seconds.
WARNING! Make sure that it is safe to continue operation in case of
a communication break.
Defines the time delay for the fieldbus communication break supervision. See
parameter
3018
COMM FAULT FUNC.
Delay time
Defines a fault level for analog input AI1. If parameter
FUNCTION is set to FAULT, the drive trips on fault AI1 LOSS, when the
analog input signal falls below the set level.
Do not set this limit below the level defined by parameter
AI1.
Value in percent of the full signal range
Defines a fault level for analog input AI2. If parameter
FUNCTION is set to FAULT, the drive trips on fault AI2 LOSS, when the
analog input signal falls below the set level.
Do not set this limit below the level defined by parameter
AI2.
Value in percent of the full signal range
Selects how the drive reacts when incorrect input power and motor cable
connection is detected (i.e. the input power cable is connected to the motor
connection of the drive).
Note: Changing this parameter setting is not recommended in normal use.
The protection is to be disabled only with corner-grounded delta power
systems and very long cables.
No action
The drive trips on fault OUTP WIRING.
Automatic fault reset. Automatic resets are possible only for certain fault
types and when the automatic reset function is activated for that fault type.
Defines the number of automatic fault resets the drive performs within the
time defined by parameter
If the number of automatic resets exceeds the set number (within the trial
time), the drive prevents additional automatic resets and remains stopped.
The drive must be reset from control panel or from a source selected by
parameter
1604
FAULT RESET SEL.
Example: Three faults have occurred during the trial time defined by
parameter 3102. Last fault is reset only if the number defined by parameter
3101 is 3 or more.
Trial time
X
X X
Number of the automatic resets
Defines the time for the automatic fault reset function. See parameter
NR OF TRIALS.
Time
3102
TRIAL TIME.
t
x = Automatic reset
Def, FbEq
3
3
1 = 0.1 s
3001
AI<MIN
0
1301
MINIMUM
1 = 0.1%
3001
AI<MIN
0
1304
MINIMUM
1 = 0.1%
ENABLE
0
1
0
1 = 1
3101
30
1 = 0.1 s
Actual signals and parameters
201