276
CODE
ALARM
2024
ENCODER ERR
(7301)
0306
bit 6
(programmable
fault function 5003)
2025
FIRST START
0309
bit 8
2026
INPUT PHASE
LOSS
(3130)
0306
bit 5
(programmable
fault function 3016)

Alarms generated by the Basic Control Panel

The Basic Control Panel indicates Control Panel alarms with a code, A5xxx.
ALARM CODE
CAUSE
5001
Drive is not responding.
5002
Incompatible communication profile
5010
Corrupted panel parameter backup file
5011
Drive is controlled from another source.
5012
Direction of rotation is locked.
5013
Panel control is disabled because start inhibit is
active.
5014
Panel control is disabled because of drive fault.
5015
Panel control is disabled because local control
mode lock is active.
5018
Parameter default value is not found.
5019
Writing non-zero parameter value is prohibited.
5020
Parameter or parameter group does not exist or
parameter value is inconsistent.
5021
Parameter or parameter group is hidden.
5022
Parameter is write protected.
5023
Parameter change is not allowed, when drive is
running.
5024
Drive is executing task.
5025
Software is being uploaded or downloaded.
5026
Value is at or below minimum limit.
5027
Value is at or above maximum limit.
5028
Invalid value
Fault tracing
CAUSE
Communication fault
between pulse encoder
and pulse encoder
interface module or
between module and drive.
Motor identification
magnetisation is on. This
alarm belongs to normal
start-up procedure.
Intermediate circuit DC
voltage is oscillating due to
missing input power line
phase or blown fuse.
Alarm is generated when
DC voltage ripple exceeds
14% of nominal DC
voltage.
WHAT TO DO
Check pulse encoder and its wiring, pulse encoder interface
module and its wiring and parameter group
settings.
Wait until drive indicates that motor identification is
completed.
Check input power line fuses.
Check for input power supply imbalance.
Check fault function parameters.
WHAT TO DO
Check panel connection.
Contact your local ABB representative.
Retry parameter upload.
Retry parameter download.
Change drive control to local control mode.
Enable change of direction. See parameter
1003
DIRECTION.
Deactivate start inhibit and retry. See
parameter
2108
Reset drive fault and retry.
Deactivate local control mode lock and retry.
See parameter
Contact your local ABB representative.
Only parameter reset is allowed.
Contact your local ABB representative.
Contact your local ABB representative.
Parameter value is read-only and cannot be
changed.
Stop drive and change parameter value.
Wait until task is completed.
Wait until upload/download is complete.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
50 ENCODER
START INHIBIT.
1606
LOCAL LOCK.