ABB ACS350 User Manual page 281

Hide thumbs Also See for ACS350:
Table of Contents

Advertisement

CODE
FAULT
0028
SERIAL 1 ERR
(7510)
0306
bit 11
(programmable fault
function 3018, 3019)
0030
FORCE TRIP
(FF90)
0306
bit 13
0034
MOTOR PHASE
(FF56)
0306
bit 14
0035
OUTP WIRING
(FF95)
0306
bit 15
(programmable fault
function 3023)
0036
INCOMPATIBLE SW
(630F)
0307
bit 3
0101
SERF CORRUPT
(FF55)
0307
bit 14
0103
SERF MACRO
(FF55)
0307
bit 14
0201
DSP T1 OVERLOAD
(6100)
0307
bit 13
0202
DSP T2 OVERLOAD
(6100)
0307
bit 13
0203
DSP T3 OVERLOAD
(6100)
0307
bit 13
0204
DSP STACK ERROR
(6100)
0307
bit 12
0206
MMIO ID ERROR
(5000)
0307
bit 11
CAUSE
Fieldbus communication break
Trip command received from
fieldbus
Motor circuit fault due to
missing motor phase or motor
thermistor relay (used in motor
temperature measurement)
fault.
Incorrect input power and motor
cable connection (i.e. input
power cable is connected to
drive motor connection).
Loaded software is not
compatible.
Drive internal error
WHAT TO DO
Check status of fieldbus communication. See chapter
Fieldbus control with fieldbus adapter/Fieldbus
control with embedded fieldbus
fieldbus adapter manual.
Check fault function parameter settings.
Check connections.
Check if master can communicate.
See appropriate communication module manual.
Check motor and motor cable.
Check motor thermistor relay (if used).
Check input power connections.
Check fault function parameters.
Contact your local ABB representative.
Write down fault code and contact your local ABB
representative.
281
or appropriate
Fault tracing

Advertisement

Table of Contents
loading

Table of Contents