260
The following table and the state diagram later in this section describe the Status
Word content for the ABB Drives profile. The upper case boldface text refers to the
states shown in the following block diagram
Bit
Name
0
RDY_ON
1
RDY_RUN
2
RDY_REF
3
TRIPPED
4
OFF_2_STA
5
OFF_3_STA
6
SWC_ON_INHIB
7
ALARM
8
AT_SETPOINT
9
REMOTE
10
ABOVE_LIMIT
11
EXT CTRL LOC
12
EXT RUN ENABLE 1
13...
Reserved
15
Fieldbus control with embedded fieldbus
ABB Drives profile (EFB) Status Word (par. 5320)
Value
(Correspond to states/boxes in the state diagram)
1
READY TO SWITCH ON
0
NOT READY TO SWITCH ON
1
READY TO OPERATE
0
OFF1 ACTIVE
1
OPERATION ENABLED
0
OPERATION INHIBITED
0...1
FAULT. See chapter
0
No fault
1
OFF2 inactive
0
OFF2 ACTIVE
1
OFF3 inactive
0
OFF3 ACTIVE
1
SWITCH-ON INHIBITED
0
Switch-on inhibit not active
1
Alarm. See chapter
0
No alarm
1
OPERATING. Actual value equals reference value (= is within tolerance limits, i.e in
speed control the speed error is less than or equal to 4/1%* of the nominal motor
speed).
* Asymmetric hysteresis: 4% when speed enters the reference area, 1% when
speed exits the reference area.
0
Actual value differs from reference value (= is outside tolerance limits).
1
Drive control location: REMOTE (EXT1 or EXT2)
0
Drive control location: LOCAL
1
Supervised parameter value exceeds the supervision high limit. Bit value is 1 until
the supervised parameter value falls below the supervision low limit. See parameter
group
32
SUPERVISION.
0
Supervised parameter value falls below the supervision low limit. Bit value is 0 until
the supervised parameter value exceeds the supervision high limit. See parameter
group
32
SUPERVISION.
1
External control location EXT2 selected
0
External control location EXT1 selected
External Run Enable signal received
0
No External Run Enable received
STATE/Description
Fault
tracing.
Fault
tracing.