ABB ACS350 User Manual page 263

Hide thumbs Also See for ACS350:
Table of Contents

Advertisement

Bit
Name
16
FBLOCAL_CTL
17
FBLOCAL_REF
18
START_DISABLE1
19
START_DISABLE2
20
JOGGING 1
21
JOGGING 2
22...26 Reserved
27
REF_CONST
28
REF_AVE
29
LINK_ON
30
REQ_STARTINH
31
Reserved
DCU PROFILE Control Word (par. 0302)
Value
1
Fieldbus local mode for Control Word requested.
Example: If the drive is in remote control and the start/stop/direction command
source is DI for external control location 1 (EXT1): by setting bit 16 to value 1,
the start/stop/direction is controlled by the fieldbus command word.
0
No fieldbus local mode
1
Fieldbus local mode Control Word for reference requested. See example in bit
16 FBLOCAL_CTL.
0
No fieldbus local mode
1
No Start Enable
0
Enable start. Effective if parameter
1
No Start Enable
0
Enable start. Effective if parameter
1
Activate jogging 1. Effective if parameter
Jogging
on page 129.
0
Jogging 1 disabled
1
Activate jogging 2. Effective if parameter
Jogging
on page 129.
0
Jogging 2 disabled
1
Constant speed reference request.
This is an internal control bit. Only for supervision.
0
No operation
1
Average speed reference request.
This is an internal control bit. Only for supervision.
0
No operation
1
Master detected on fieldbus link.
This is an internal control bit. Only for supervision.
0
Fieldbus link is down.
1
Start inhibit
0
No start inhibit
Information
1608
setting is COMM.
1609
setting is COMM.
1010
setting is COMM. See section
1010
setting is COMM. See section
Fieldbus control with embedded fieldbus
263