Parameters – complete descriptions
Index Name/Selection

25 CRITICAL SPEEDS

2501
CRIT SPEED SEL
OFF
ON
2502
CRIT SPEED 1 LO
0.0...500.0 Hz /
0...30000 rpm
2503
CRIT SPEED 1 HI
0.0...500.0 Hz /
0...30000 rpm
2504
CRIT SPEED 2 LO
0.0...500.0 Hz /
0...30000 rpm
2505
CRIT SPEED 2 HI
0.0...500.0 Hz /
0...30000 rpm
2506
CRIT SPEED 3 LO
0.0...500.0 Hz /
0...30000 rpm
2507
CRIT SPEED 3 HI
0.0...500.0 Hz /
0...30000 rpm

26 MOTOR CONTROL

2601
FLUX OPT ENABLE
Actual signals and parameters
Description
Speed bands within which the drive is not allowed to operate.
Activates/deactivates the critical speeds function. The critical speed function
avoids specific speed ranges.
Example: A fan has vibrations in the range of 18 to 23 Hz and 46 to 52 Hz.
To make the drive to jump over the vibration speed ranges:
- Activate the critical speeds function.
- Set the critical speed ranges as in the figure below.
f
(Hz)
output
52
46
23
18
1 2 3 4
Inactive
Active
Defines the minimum limit for critical speed/frequency range 1.
Limit in rpm. Limit in Hz if parameter
SCALAR:FREQ. The value cannot be above the maximum (parameter
CRIT SPEED 1 HI).
Defines the maximum limit for critical speed/frequency range 1.
Limit in rpm. Limit in Hz if parameter
SCALAR:FREQ. The value cannot be below the minimum (parameter
CRIT SPEED 1 LO).
See parameter
2502
CRIT SPEED 1 LO.
See parameter 2502.
See parameter
2503
CRIT SPEED 1 HI.
See parameter 2503.
See parameter
2502
CRIT SPEED 1 LO.
See parameter 2502.
See parameter
2503
CRIT SPEED 1 HI.
See parameter 2503.
Motor control variables
Activates/deactivates the flux optimisation function. Flux optimisation
reduces the total energy consumption and motor noise level when the drive
operates below the nominal load. The total efficiency (motor and the drive)
can be improved by 1% to 10%, depending on the load torque and speed.
The disadvantage of this function is that the dynamic performance of the
drive is weakened.
1
Par.
2502
= 18 Hz
2
Par.
2503
= 23 Hz
3
Par.
2504
= 46 Hz
4
Par.
2505
= 52 Hz
f
(Hz)
reference
9904
MOTOR CTRL MODE setting is
9904
MOTOR CTRL MODE setting is
Def, FbEq
OFF
0
1
0
1 = 0.1 Hz /
2503
1 rpm
0
1 = 0.1 Hz /
2502
1 rpm
0
1 = 0.1 Hz /
1 rpm
0
1 = 0.1 Hz /
1 rpm
0
1 = 0.1 Hz /
1 rpm
0
1 = 0.1 Hz /
1 rpm
OFF