224
Parameters – complete descriptions
Index Name/Selection
4306
RUNTIME FREQ LVL
0.0...100.0%

50 ENCODER

5001
PULSE NR
32...16384 ppr
5002
ENCODER ENABLE
DISABLE
ENABLE
5003
ENCODER FAULT
FAULT
ALARM
5010
Z PLS ENABLE
DISABLE
ENABLE
5011
POSITION RESET
DISABLE
ENABLE
51 EXT COMM
MODULE
5101
FBA TYPE
NOT DEFINED
PROFIBUS-DP
CANopen
DEVICENET
5102
FB PAR 2
...
....
5126
FB PAR 26
5127
FBA PAR REFRESH
DONE
REFRESH
Actual signals and parameters
Description
Defines the brake close speed. When frequency falls below the set level
during run, the brake is closed. The brake is re-opened when the
requirements set by parameters
Value in percent of the maximum frequency (with scalar control) or the
maximum speed (with vector control). If parameter value is set to zero, the
function is disabled. The control mode is selected by parameter
MOTOR CTRL MODE.
Encoder connection.
For more information, see MTAC-01 Pulse Encoder Interface Module User's
Manual [3AFE68591091 (English)].
States the number of encoder pulses per one revolution.
Pulse number in pulses per round (ppr)
Enables the encoder.
Disabled
Enabled
Defines the operation of the drive if a failure is detected in communication
between the pulse encoder and the pulse encoder interface module, or
between the module and the drive.
The drive trips on fault ENCODER ERR.
The drive generates alarm ENCODER ERROR.
Enables the encoder zero (Z) pulse. Zero pulse is used for position reset.
Disabled
Enabled
Enables the position reset.
Disabled
Enabled
The parameters need to be adjusted only when a fieldbus adapter module
(optional) is installed and activated by parameter
For more details on the parameters, refer to the manual of the fieldbus
module and chapter
Fieldbus control with fieldbus
settings will remain the same even though the macro is changed.
Note: In adapter module the parameter group number is 1.
Displays the type of the connected fieldbus adapter module.
Fieldbus module is not found, or it is not properly connected, or parameter
9802
COMM PROT SEL setting is not EXT FBA.
Profibus adapter module
CANopen adapter module
DeviceNet adapter module
These parameters are adapter module-specific. For more information, see
the module manual. Note that not all of these parameters are necessarily
visible.
Validates any changed adapter module configuration parameter settings.
After refreshing, the value reverts automatically to DONE.
Refreshing done
Refreshing
4301...4305
are met.
9802
COMM PROT SEL.
adapter. These parameter
Def, FbEq
0
1 = 0.1%
9904
1024
1 = 1
DISABLE
0
1
FAULT
1
2
DISABLE
0
1
DISABLE
0
1
0
1
32
37
0
1