Actual signals
No.
Name/Value
0169
SEQ PROG TIMER
0170
SEQ PROG AO VAL
0171
SEQ CYCLE CNTR
0172
ABS TORQUE

03 FB ACTUAL SIGNALS

0301
FB CMD WORD 1
0302
FB CMD WORD 2
0303
FB STS WORD 1
0304
FB STS WORD 2
0305
FAULT WORD 1
0306
FAULT WORD 2
Description
Current state time counter of the sequence programming
Analog output control values defined by sequence programming. See
parameter
8423
ST1 OUT CONTROL.
Executed sequence counter of the sequence programming. See
parameters
8415
CYCLE CNT LOC and
Calculated absolute value of the motor torque in percent of the motor
nominal torque
Data words for monitoring the fieldbus communication (read-only). Each
signal is a 16-bit data word.
Data words are displayed on the panel in hexadecimal format.
A 16-bit data word. See section
A 16-bit data word. See section
A 16-bit data word. See section
A 16-bit data word. See section
A 16-bit data word. For the possible causes and remedies and fieldbus
equivalents, see chapter
Fault
Bit 0 = OVERCURRENT
Bit 1 = DC OVERVOLT
Bit 2 = DEV OVERTEMP
Bit 3 = SHORT CIRC
Bit 4 = Reserved
Bit 5 = DC UNDERVOLT
Bit 6 = AI1 LOSS
Bit 7 = AI2 LOSS
Bit 8= MOT OVERTEMP
Bit 9 = PANEL LOSS
Bit 10 = ID RUN FAIL
Bit 11 = MOTOR STALL
Bit 12 = Reserved
Bit 13 = EXT FAULT 1
Bit 14 = EXT FAULT 2
Bit 15 = EARTH FAULT
A 16-bit data word. For the possible causes and remedies and fieldbus
equivalents, see chapter
Fault
Bit 0 = UNDERLOAD
Bit 1 = THERM FAIL
Bit 2...3 = Reserved
Bit 4 = CURR MEAS
Bit 5 = SUPPLY PHASE
Bit 6 = ENCODER ERR
Bit 7 = OVERSPEED
Bit 8 = Reserved
8416
CYCLE CNT RST.
DCU communication profile
DCU communication profile
DCU communication profile
DCU communication profile
tracing.
tracing.
Actual signals and parameters
145
FbEq
1 = 0.1%
1 = 1
1 = 0.1%
on page 262.
on page
262
on page 262.
on page
262