It is also possible to monitor motor temperature by connecting a PTC sensor and
a thermistor relay between the +24 VDC voltage supply offered by the drive and
digital input. The figure below displays the connection.
Par. 3501 = THERM(0) or THERM(1)
Thermistor
relay
T
Motor
WARNING! According to IEC 664, the connection of the motor thermistor to the
digital input requires double or reinforced insulation between motor live parts and the
thermistor. Reinforced insulation entails a clearance and creeping distance of 8 mm
(400 / 500 VAC equipment).
If the thermistor assembly does not fulfill the requirement, the other I/O terminals of
the drive must be protected against contact, or a thermistor relay must be used to
isolate the thermistor from the digital input.

Settings

Parameter
13 ANALOGUE INPUTS
15 ANALOGUE OUTPUTS
35 MOTOR TEMP MEAS
Other
At the motor end the cable shield should be earthed through a 10 nF capacitor. If this is not possible,
the shield is to be left unconnected.

Diagnostics

Actual values
0145
Alarm/Fault
MOTOR TEMP/MOT OVERTEMP
DI1...5
+24 VDC
Additional information
Analog input settings
Analog output settings
Motor temperature measurement settings
Additional information
Motor temperature
Additional information
Excessive motor temp
125