174
Parameters – complete descriptions
Index Name/Selection
1607
PARAM SAVE
DONE
SAVE...
1608
START ENABLE 1
NOT SEL
DI1
DI2
DI3
DI4
DI5
Actual signals and parameters
Description
Saves the valid parameter values to the permanent memory.
Note: A new parameter value of a standard macro is saved automatically
when changed from the panel but not when altered through a fieldbus
connection.
Saving completed
Saving in progress
Selects the source for the Start Enable 1 signal.
Note: Functionality of the Start Enable signal is different from the Run Enable
signal.
Example: External damper control application using Start Enable and Run
Enable. Motor can start only after the damper is fully open.
Drive started
Relay energized
Relay
de-energized
Damper
closed
Damper
opening
time
Motor
speed
Start Enable signal is on.
External signal required through digital input DI1. 1 = Start Enable. If Start
Enable signal is switched off, the drive will not start or it coasts to stop if it is
running and alarm START ENABLE 1 MISSING is activated.
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1.
Damper open
Damper
closed
Damper
closing
time
Run Enable signal
from the damper end
switch when the
damper is fully opened.
(1601)
Acceleration
Deceleration
time (2202)
time (2203)
Def, FbEq
DONE
0
1
NOT SEL
Start/Stop
command
(group 10)
Start Enable
signals
(1608 and 1609)
Started
output status
(group 14)
Damper
status
Motor status
0
1
2
3
4
5