IDENTIFICATION MAGNETIZATION WITH ID RUN SELECTION 0 (OFF)
Press key
to switch to local control (LOC shown on the
LOC
REM
left).
Press
to start the drive. The motor model is now
calculated by magnetizing the motor for 10 to 15 s at zero
speed.
Check the direction of the motor rotation.
• If the drive is in remote control (REM shown on the left),
switch to local control by pressing
• To go to the Main menu, press
OUTPUT; otherwise press
MENU at the bottom.
• Press keys
/
• Increase the frequency reference from zero to a small value
with key
.
• Press
to start the motor.
• Check that the actual direction of the motor is the same as
indicated on the display (FWD means forward and REV
reverse).
• Press
to stop the motor.
To change the direction of the motor rotation:
• Disconnect input power from the drive, and wait 5 minutes
for the intermediate circuit capacitors to discharge. Measure
the voltage between each input terminal (U1, V1 and W1)
and earth with a multimeter to ensure that the drive is
discharged.
• Exchange the position of two motor cable phase conductors
at the drive output terminals or at the motor connection box.
• Verify your work by applying input power and repeating the
check as described above.
SPEED LIMITS AND ACCELERATION/DECELERATION TIMES
Set the minimum speed (parameter 2001).
Set the maximum speed (parameter 2002).
Set the acceleration time 1 (parameter 2202).
Note: Check also acceleration time 2 (parameter 2205) if two
acceleration times will be used in the application.
DIRECTION OF THE MOTOR ROTATION
.
LOC
REM
if the bottom line shows
repeatedly until you see
until you see "rEF" and press
xxx
LOC
.
forward
direction
reverse
direction
2001
LOC
PAR
2002
LOC
PAR
2202
LOC
PAR
Start-up, control with I/O and ID Run
49
.
Hz
SET
FWD
FWD
FWD
FWD