Drive control parameters

After the fieldbus communication has been set up, the drive control parameters
listed in the table below should be checked and adjusted where necessary.
The Setting for fieldbus control column gives the value to use when the fieldbus
interface is the desired source or destination for that particular signal. The Function/
Information column gives a description of the parameter.
Parameter
CONTROL COMMAND SOURCE SELECTION
1001
EXT1 COMMANDS
1002
EXT2 COMMANDS
1003
DIRECTION
1010
JOGGING SEL
1102
EXT1/EXT2 SEL
1103
REF1 SELECT
1106
REF2 SELECT
OUTPUT SIGNAL SOURCE SELECTION
1401
RELAY OUTPUT 1
1501
AO1 CONTENT
SEL
SYSTEM CONTROL INPUTS
1601
RUN ENABLE
1604
FAULT RESET SEL
1606
LOCAL LOCK
1607
PARAM SAVE
1608
START ENABLE 1
1609
START ENABLE 2
LIMITS
2013
MIN TORQUE SEL
2014
MAX TORQUE SEL
2201
ACC/DEC 1/2 SEL
2209
RAMP INPUT 0
Setting for
Function/Information
fieldbus control
COMM
Selects fieldbus as the source for the start and stop commands when
EXT1 is selected as the active control location.
COMM
Selects fieldbus as the source for the start and stop commands when
EXT2 is selected as the active control location.
FORWARD
Enables rotation direction control as defined by parameters 1001 and
REVERSE
1002. The direction control is explained in section
REQUEST
handling. on page 254.
COMM
Enables jogging 1 or 2 activation through fieldbus.
COMM
Enables EXT1/EXT2 selection through fieldbus.
COMM
Fieldbus reference REF1 is used when EXT1 is selected as the active
control location. See section
COMM+AI1
DCU profile) on page 249.
COMM*AI1
COMM
Fieldbus reference REF2 is used when EXT2 is selected as the active
control location. See section
COMM+AI1
DCU profile) on page 249.
COMM*AI1
COMM
Enables relay output RO control by signal
COMM(-1)
135 (i.e
0135
Directs the contents of fieldbus reference
COMM VALUE 1)
analog output AO.
COMM
Selects fieldbus interface as the source for the inverted Run Enable
signal (Run Disable).
COMM
Selects fieldbus interface as the source for the fault reset signal.
COMM
Selects fieldbus interface as the source for the local lock signal.
DONE; SAVE
Saves parameter value changes (including those made through
fieldbus control) to permanent memory.
COMM
Selects fieldbus interface as the source for the inverted Start Enable 1
(Start Disable) signal.
COMM
Selects fieldbus interface as the source for the inverted Start Enable 2
(Start Disable) signal.
COMM
Selects fieldbus interface as the source for the minimum torque limit
1/2 selection.
COMM
Selects fieldbus interface as the source for the maximum torque limit
1/2 selection.
COMM
Selects fieldbus interface as the source for acceleration/deceleration
ramp pair 1/2 selection
COMM
Selects fieldbus interface as the source for forcing ramp input to zero.
Reference
Reference selection and correction
Reference selection and correction
0134
COMM RO WORD.
0135
COMM VALUE 1 to
Fieldbus control with fieldbus adapter
269
(for
(for