Parameters – complete descriptions
Index Name/Selection
ON
9912
MOTOR NOM
TORQUE
-
9913
MOTOR POLE PAIRS Calculated motor pole pair number (calculation is based on parameter
-
Description
ID Run. Guarantees the best possible control accuracy. The ID Run takes
about one minute. An ID Run is especially effective when:
- vector control mode is used [parameter
2 (VECTOR:TORQ)], and
- operation point is near zero speed and/or
- operation requires a torque range above the motor nominal torque, over a
wide speed range, and without any measured speed feedback (i.e without a
pulse encoder).
Note: The motor must be de-coupled from the driven equipment.
Note: Check the direction of rotation of the motor before starting the ID Run.
During the run, the motor will rotate in the forward direction.
Note: If motor parameters are changed after ID Run, repeat the ID Run.
WARNING! The motor will run at up to approximately 50...80% of
the nominal speed during the ID Run. ENSURE THAT IT IS SAFE
TO RUN THE MOTOR BEFORE PERFORMING THE ID RUN!
Calculated motor nominal torque in N·m (calculatIon is based on parameter
9909
MOTOR NOM POWER and
Read-only
MOTOR NOM FREQ and
Read-only
9904
= 1 (VECTOR:SPEED) or
9908
MOTOR NOM SPEED values).
9908
MOTOR NOM SPEED values).
Def, FbEq
1
0
1 = 0.1 N·m
9907
0
1 = 1