ST8 (error state): Drive is stopped with ramp pair 1. Relay output RO is activated. If
sequence programming is deactivated by falling edge of digital input DI1, state
machine is reset to state 1. New start command can be activated by digital input DI1
or by digital inputs DI4 and DI5 (both inputs DI4 and DI5 must be simultaneously
active).
1)
0 second ramp time = drive is accelerated/decelerated as rapidly as possible.
2)
State reference must be between 0...100%, i.e scaled AI1 value must be between
15...85%. If AI1 = 0 reference = 0% + 35% -50% = -15% < 0%.
Parameter
1002
EXT2 COMMANDS
1102
EXT1/EXT2 SEL
1106
REF2 SELECT
1201
CONST SPEED SEL NOT SEL
1401
RELAY OUTPUT 1
1601
RUN ENABLE
1805
DO SIGNAL
2102
STOP FUNCTION
2201
ACC/DEC 1/2 SEL
2202
ACCELER TIME 1
2203
DECELER TIME 1
2205
ACCELER TIME 2
2206
DECELER TIME 2
2207
RAMP SHAPE 2
3201
SUPERV 1 PARAM
3202
SUPERV 1 LIM LO
3203
SUPERV 1 LIM HI
8401
SEQ PROG ENABLE EXT2
8402
SEQ PROG START
8404
SEQ PROG RESET
8406
SEQ LOGIC VAL 1
8407
SEQ LOGIC OPER 1 AND
8408
SEQ LOGIC VAL 2
8415
CYCLE CNT LOC
8416
CYCLE CNT RST
Program features
Setting
Additional information
SEQ PROG
Start, stop, direction commands for EXT2
EXT2
EXT2 activation
AI1+SEQ PROG
Addition of analog input AI1 and sequence programming output as
REF2
Deactivation of constant speeds
SEQ PROG
Relay output RO control as defined by parameter 8423/.../8493
NOT SEL
Deactivation of Run Enable
SEQ PROG
Digital output DO control as defined by parameter 8423/.../8493
RAMP
Ramp stop
SEQ PROG
Ramp as defined by parameter 8422/.../8492
1 s
Acceleration/deceleration ramp pair 1
0 s
20 s
Acceleration/deceleration ramp pair 2
20 s
5 s
Shape of the acceleration/deceleration ramp 2
171
Sequence counter (signal
30
Supervision low limit
30
Supervision high limit
Sequence programming enabled in EXT2
DI1
Sequence programming activation through digital input (DI1)
DI1(INV)
Sequence programming reset through inverted digital input DI1(INV)
DI4
Logic value 1
Operation between logic value 1 and 2
DI5
Logic value 2
ST5 TO NEXT
Sequence counter activation, i.e. sequence count increases every time
the state changes from state 5 to state 6.
STATE 1
Sequence counter reset during state transition to state 1
0171
SEQ CYCLE CNTR) supervision