Fault messages generated by the drive

CODE
FAULT
0001
OVERCURRENT
(2310)
0305
bit 0
0002
DC OVERVOLT
(3210)
0305
bit 1
0003
DEV OVERTEMP
(4210)
0305
bit 2
0004
SHORT CIRC
(2340)
0305
bit 3
0006
DC UNDERVOLT
(3220)
0305
bit 5
0007
AI1 LOSS
(8110)
0305
bit 6
(programmable fault
function 3001, 3021)
0008
AI2 LOSS
(8110)
0305
bit 7
(programmable fault
function 3001, 3022)
Fault tracing
CAUSE
Output current has exceeded
trip level.
Excessive intermediate circuit
DC voltage. DC overvoltage trip
limit is 420 V for 200 V drives
and 840 V for 400 V drives.
Drive IGBT temperature is
excessive. Fault trip limit is
135°C.
Short circuit in motor cable(s) or
motor
Intermediate circuit DC voltage
is not sufficient due to missing
input power line phase, blown
fuse, rectifier bridge internal
fault or too low input power.
Analog input AI1 signal has
fallen below limit defined by
parameter
3021
AI1 FAULT
LIMIT.
Analog input AI2 signal has
fallen below limit defined by
parameter
3022
AI2 FAULT
LIMIT.
WHAT TO DO
Check motor load.
Check acceleration time
(2202
Check motor and motor cable (including phasing).
Check ambient conditions. Load capacity decreases
if installation site ambient temperature exceeds
40°C. See section
Derating
Check that overvoltage controller is on (parameter
2005
OVERVOLT CTRL).
Check input power line for static or transient
overvoltage.
Check brake chopper and resistor (if used). DC
overvoltage control must be deactivated when brake
chopper and resistor is used.
Check deceleration time (2203, 2206).
Retrofit frequency converter with brake chopper and
brake resistor.
Check ambient conditions. See also section
on page 291.
Check air flow and fan operation.
Check motor power against unit power.
Check motor and motor cable.
Check that undervoltage controller is on (parameter
2006
UNDERVOLT CTRL).
Check input power supply and fuses.
Check fault function parameter settings.
Check for proper analog control signal levels.
Check connections.
Check fault function parameter settings.
Check for proper analog control signal levels.
Check connections.
and 2205).
on page 291.
Derating