Parameters – complete descriptions
Index Name/Selection
DI3,4
DI4,5
DI1(INV)
DI2(INV)
DI3(INV)
DI4(INV)
DI5(INV)
DI1,2(INV)
DI2,3(INV)
DI3,4(INV)
DI4,5(INV)
1606
LOCAL LOCK
NOT SEL
DI1
DI2
DI3
DI4
DI5
ON
COMM
DI1(INV)
DI2(INV)
DI3(INV)
DI4(INV)
DI5(INV)
Description
See selection DI1,2.
See selection DI1,2.
User Parameter Set control through inverted digital input DI1. Falling edge of
inverted digital input DI1: User Parameter Set 2 is loaded into use. Rising
edge of inverted digital input DI1: User Parameter Set 1 is loaded into use.
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
User Parameter Set selection through inverted digital inputs DI1 and DI2. 1 =
DI inactive, 0 =DI active.
DI1 DI2 User Parameter Set
1
1 User Parameter Set 1
0
1 User Parameter Set 2
1
0 User Parameter Set 3
See selection DI1,2(INV).
See selection DI1,2(INV).
See selection DI1,2(INV).
Disables entering local control mode or selects the source for the local
control mode lock signal. When local lock is active, entering the local control
mode is disabled (LOC/REM key of the panel).
Local control is allowed.
Local control mode lock signal through digital input DI1. Rising edge of digital
input DI1: Local control disabled. Falling edge of digital input DI1: Local
control allowed.
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1.
Local control is disabled.
Fieldbus interface as the source for the local lock, i.e. control word
CMD WORD 1 bit 14. The control word is sent by the fieldbus controller via
the fieldbus adapter or embedded fieldbus (modbus) to the drive. For the
control word bits, see section
Note: This setting applies only for the DCU profile!
Local lock through inverted digital input DI1. Rising edge of inverted digital
input DI1: Local control allowed. Falling edge of inverted digital input DI1:
Local control disabled.
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
DCU communication profile
Def, FbEq
9
10
-1
-2
-3
-4
-5
-7
-8
-9
-10
NOT SEL
0
1
2
3
4
5
7
0301
FB
8
on page 262.
-1
-2
-3
-4
-5
Actual signals and parameters
173

Advertisement

Table of Contents