Parameters – complete descriptions
Index Name/Selection
1506
FILTER AO1
0.0...10.0 s
16 SYSTEM
CONTROLS
1601
RUN ENABLE
NOT SEL
DI1
DI2
DI3
DI4
DI5
COMM
DI1(INV)
DI2(INV)
DI3(INV)
DI4(INV)
DI5(INV)
1602
PARAMETER LOCK
LOCKED
OPEN
NOT SAVED
1603
PASS CODE
0...65535
1604
FAULT RESET SEL
KEYPAD
DI1
DI2
Description
Defines the filter time constant for analog output AO, i.e the time within 63%
of a step change is reached. See figure in parameter
Filter time constant
Run Enable, parameter lock etc.
Selects a source for the external Run Enable signal.
Allows the drive to start without an external Run Enable signal.
External signal required through digital input DI1. 1 = Run Enable. If Run
Enable signal is switched off, the drive will not start or coasts to stop if it is
running.
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1.
Fieldbus interface as the source for inverted Run Enable signal (Run
Disable), i.e. control word
profile
5319
EFB PAR 19 bit 3). The control word is sent by the fieldbus
controller via the fieldbus adapter or embedded fieldbus (modbus) to the
drive. For the control word bits, see sections
page
262
and
ABB Drives communication profile
External signal required through inverted digital input DI1. 0 = Run Enable.
If Run Enable signal is switched on, the drive will not start or coasts to stop if
it is running.
See selection DI1(INV)
See selection DI1(INV)
See selection DI1(INV)
See selection DI1(INV)
Selects the state of the parameter lock. The lock prevents parameter
changing from control panel.
Parameter values cannot be changed from the control panel. The lock can be
opened by entering the valid code to parameter
The lock does not prevent parameter changes made by macros or fieldbus.
The lock is open. Parameter values can be changed.
Parameter changes made by control panel are not stored into the permanent
memory. To store changed parameter values, set parameter
SAVE value to SAVE.
Selects the pass code for the parameter lock (see parameter
PARAMETER LOCK).
Pass code. Setting 358 opens the lock. The value reverts back to 0
automatically.
Selects the source for the fault reset signal. The signal resets the drive after a
fault trip if the cause of the fault no longer exists.
Fault reset only from the control panel
Reset through digital input DI1 (reset by a rising edge of DI1) or by control
panel
See selection DI1.
0301
FB CMD WORD 1 bit 6 (with ABB drives
DCU communication profile
on page 258.
1603
Def, FbEq
0.1
1303
FILTER AI1.
1 = 0.1 s
NOT SEL
0
1
2
3
4
5
7
on
-1
-2
-3
-4
-5
OPEN
0
PASS CODE.
1
2
1607
PARAM
1602
0
1 = 1
KEYPAD
0
1
2
Actual signals and parameters