The following table and the state diagram later in this section describe the Control
Word content for the ABB Drives profile. The upper case boldface text refers to the
states shown in the following block diagram
Bit
Name
0
OFF1
CONTROL
1
OFF2
CONTROL
2
OFF3
CONTROL
3
INHIBIT
OPERATION
4
Note: Bit 4 is supported only by ABB DRV FULL profile!
RAMP_OUT_
ZERO (ABB
DRV FULL)
5
RAMP_HOLD
6
RAMP_IN_
ZERO
7
RESET
8...9
Not in use
10
Note: Bit 10 is supported only by ABB DRV FULL profile!
REMOTE_CMD
(ABB DRV
FULL)
11
EXT CTRL LOC
12...15
Reserved
ABB Drives profile Control Word (parameter 5319)
Value
1
Enter READY TO OPERATE.
0
Stop along currently active deceleration ramp (2203/2206). Enter OFF1 ACTIVE;
proceed to READY TO SWITCH ON unless other interlocks (OFF2, OFF3) are
active.
1
Continue operation (OFF2 inactive).
0
Emergency OFF, drive coast to stop.
Enter OFF2 ACTIVE; proceed to SWITCH-ON INHIBITED.
1
Continue operation (OFF3 inactive).
0
Emergency stop, drive stops within time defined by par. 2208. Enter OFF3 ACTIVE;
proceed to SWITCH-ON INHIBITED.
Warning: Ensure motor and driven machine can be stopped using this stop mode.
1
Enter OPERATION ENABLED. (Note: The Run Enable signal must be active; see
parameter 1601. If par. 1601 is set to COMM, this bit also activates the Run Enable
signal.)
0
Inhibit operation. Enter OPERATION INHIBITED.
1
Enter RAMP FUNCTION GENERATOR: OUTPUT ENABLED.
0
Force Ramp Function Generator output to zero.
Drive ramps to stop (current and DC voltage limits in force).
1
Enable ramp function.
Enter RAMP FUNCTION GENERATOR: ACCELERATOR ENABLED.
0
Halt ramping (Ramp Function Generator output held).
1
Normal operation. Enter OPERATING.
0
Force Ramp Function Generator input to zero.
0=>1
Fault reset if an active fault exists. Enter SWITCH-ON INHIBITED. Effective if par.
1604
is set to COMM.
0
Continue normal operation.
1
Fieldbus control enabled.
0
Control Word
= /
0 or Reference
Control Word = 0 and Reference = 0: Fieldbus control enabled.
Reference and deceleration/acceleration ramp are locked.
1
Select external control location EXT2. Effective if
0
Select external control location EXT1. Effective if par.
Comments
= /
0: Retain last Control Word and Reference.
par.1102
1102
Fieldbus control with embedded fieldbus
259
is set to COMM.
is set to COMM.