Alternate macro

This macro provides an I/O configuration adapted to a sequence of DI control
signals used when alternating the rotation direction of the drive. To enable the
macro, set the value of parameter
For the parameter default values, see section
on page 142. If you use other than the default connections presented below, see
section

Default I/O connections

1...10 kohm
max. 500 ohm
1)
See parameter group
DI3 DI4 Operation (parameter)
0
1
0
1
I/O terminals
on page 40.
X1A
1
SCR
2
AI1
3
GND
4
+10V
5
AI2
6
GND
7
AO
8
GND
3)
9
+24V
10
GND
11
DCOM
12
DI1
13
DI2
14
DI3
15
DI4
16
DI5
X1B
17
ROCOM
18
RONC
19
RONO
20
DOSRC
21
DOOUT
22
DOGND
12 CONSTANT
0 Set speed through AI1
0 Speed 1 (1202)
1 Speed 2 (1203)
1 Speed 3 (1204)
9902
to 3 (ALTERNATE).
Default values with different macros
Signal cable shield (screen)
Motor speed reference: 0...10 V
Analog input circuit common
Reference voltage: +10 VDC, max. 10 mA
Not in use by default. 0...10 V
Analog input circuit common
Motor speed value: 0...20 mA
Analog output circuit common
Auxiliary voltage output: +24 VDC, max. 200 mA
Auxiliary voltage output common
Digital input common
Start forward: If DI1 = DI2, the drive stops.
Start reverse
Constant speed selection
Constant speed selection
Acceleration and deceleration selection
Relay output
No fault [Fault (-1)]
Digital output, max. 100 mA
No fault [Fault (-1)]
2)
SPEEDS:
0 = ramp times according to parameters
and 2203.
1 = ramp times according to parameters
and 2206.
3)
360 degree grounding under a clamp.
Tightening torque = 0.5 N·m / 4.4 lbf. in.
1)
1)
2)
2202
2205
Application macros
89