Mitsubishi Electric Q26UD(E)HCPU User Manual page 116

Melsecq series
Hide thumbs Also See for Q26UD(E)HCPU:
Table of Contents

Advertisement

(b) A6CON2
The following table lists the specifications of the FCN-363T-T005/H used for the A6CON2.
Applicable wire
size
24 AWG
26 AWG
28 AWG
Wiring of the A6CON2 requires special tools.
For usage and adjustment of the tools, contact FUJITSU COMPONENT LIMITED.
(c) A6CON3
Wiring of the A6CON3 requires special tools.
For usage and adjustment of the tools, contact FUJITSU COMPONENT LIMITED.
Arrangement for a flat cable is in the order of A1
(The following figure shows a connector seen from the plug-in side.)
114
Cross-section area of
wire
2
0.20 to 0.24mm
2
0.13 to 0.16mm
2
0.088 to 0.096mm

B20 B19 B18 B17 B16 B15 B14 B13 B12 B11 B10 B09 B08 B07 B06 B05 B04 B03 B02 B01
A20 A19 A18 A17 A16 A15 A14 A13 A12 A11 A10 A09 A08 A07 A06 A05 A04 A03 A02 A01
Crimp height
1.2 or less
1.25 to 1.30
1.2 or less
1.20 to 1.25
1.2 or less
1.15 to 1.20
1.
Check the terminal layout and press the wires
against the connector.

•••••.
B1
A2
Outside
Length of stripped
diameter of
wire part
coated wire
3.0 to 4.0
3.0 to 4.0
3.0 to 4.0