Error code
Error item
(Hexadecimal)
File-related
413D
H
error
File-related
413E
H
error
File-related
413F
H
error
Intelligent
function
414A
module
H
specification
error
Intelligent
function
414C
module
H
specification
error
File-related
4150
H
error
File-related
4151
H
error
Online
4160
registration
H
error
Online
4165
registration
H
error
Online
4166
registration
H
error
Online
4167
registration
H
error
Online
4168
registration
H
error
Online
4169
registration
H
error
Online
416A
registration
H
error
Online
416B
registration
H
error
Ethernet I/F
4170
H
Error
Ethernet I/F
4171
H
Error
418
Error details
The specified file capacity cannot be secured.
Operation is disabled for the specified drive
(memory).
The file is inhibited from write to the standard
RAM.
Operation was executed for the intelligent
function module of the non-control group in the
multiple CPU system.
The I/O address of the specified CPU module is
wrong.
An attempt was made to format the drive
protected by the system.
An attempt was made to delete the file protected
by the system.
The registered number of forced inputs/outputs
exceeded the maximum value.
The multiple-block online change system file
does not exist.
Online change (files) is disabled because it is
being executed from the same source.
Online change (files) is disabled because it is
being performed from another source.
The number of registered executional
conditioned device test settings exceeds 32.
No executional conditioned device test settings
are registered.
The specified executing condition does not exist.
(Executional conditioned device test)
The specified program is SFC program.
(Executional conditioned device test)
The password is wrong.
The port for communication use is at remote
password locking status.
Corrective action
Execute again after increasing the capacity of the
specified drive (memory).
Execute again after changing the target drive
(memory).
Execute again after changing the specified drive
(memory).
Execute the operation again from the control CPU
of the target module.
Execute again after checking the I/O address of
the specified CPU module.
Do not format the target drive (memory) as it
cannot be formatted.
Do not delete the target file as it cannot be deleted.
Deregister the unused forced inputs/outputs.
Execute again after securing the area that enables
multiple-block online change at the time of
programmable controller memory format.
Due to unsuccessful online change (files)
previously occurred for some reason (example:
communication failure), the processing is kept
incomplete.
Forcibly perform another online change (files).
Due to unsuccessful online change (files) from
another source previously occurred for some
reason (example: communication failure), the
processing is kept incomplete.
If online change (files) is not being performed by
any other programming tool, forcibly perform
another online change (files).
Disable the executional conditioned device test
settings registered in the CPU module, or
decrease the number of test settings registered for
the same step number.
Check the number of executional conditioned
device test settings registered in the CPU module,
and disable the settings.
Check whether the specified executing conditions
(program, step No. operation timing, device name)
specified when the settings were disabled are
registered.
Change the program specified when the
executional conditioned device test settings are
registered or disabled.
Check the specified remote password, then
execute the lock/unlock processing of the remote
password again.
Execute communication after unlocking the remote
password processing.
Corresponding
CPU
QCPU
LCPU
QCPU
LCPU
QCPU
LCPU
QCPU
QCPU
LCPU
QCPU
LCPU
QCPU
LCPU
QCPU
LCPU
QCPU
Qn(H)
QnPH
QnPRH
Qn(H)
QnPH
QnPRH
QCPU
LCPU
QCPU
LCPU
QCPU
LCPU
QCPU
LCPU
QCPU
LCPU
QCPU
LCPU