[LINK PARA. ERROR]
Pairing setting in CC-Link IE Controller Network
modules installed in CPUs except for redundant
CPUs was performed.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• At power-on/At reset/STOP  RUN
[LINK PARA. ERROR]
A CC-Link IE module with a version that does not
support items set in the network parameter is
mounted/connected.
3102
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• At power-on/At reset/STOP  RUN
[LINK PARA. ERROR]
• LB/LW own station send range at LB/LW4000 or
later was set.
• LB/LW setting (2) was performed.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• At power-on/At reset/STOP  RUN
[LINK PARA. ERROR]
In a multiple CPU system, Ethernet interface
module under control of another station is
specified to the start I/O number of the Ethernet
network parameter.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• At power-on/At reset/STOP  RUN
[LINK PARA. ERROR]
• Although the number of modules has been set
to one or greater number in the Ethernet module
count parameter setting, the number of actually
mounted module is zero.
• The start I/O No. of the Ethernet network
parameter differs from the I/O No. of the actually
mounted module.
3103
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• At power-on/At reset/STOP  RUN
[LINK PARA. ERROR]
• In the redundant system, although "Ethernet
(Main base)" is selected for Network type, the
Ethernet module is mounted on the extension
base unit.
• In the redundant system, although "Ethernet
(Extension base)" is selected for Network type,
the Ethernet module is mounted on the main
base unit.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• At power-on/At reset/STOP  RUN
368
Corrective action
Examine the pairing setting for the network
parameter in the control station.
• Correct and write the network parameters.
• Mount/connect a CC-Link IE module with a
version that supports items set in the
network parameter.
Correct the network range assignments of the
network parameter for the control station.
• Delete the Ethernet network parameter of
Ethernet interface module under control of
another station.
• Change the setting to the start I/O number
of Ethernet interface module under control
of the host station.
• Correct and write the network parameters.
• If an error occurs again even after it is
corrected, the cause is a hardware failure.
Please consult your local Mitsubishi
representative.
LED status,
Corresponding
CPU status
RUN: Off
Q00J/Q00/Q01
ERR.:Flashing
Qn(H)
QnPH
CPU Status:Stop
RUN: Off
ERR.:Flashing
CPU Status:Stop
RUN: Off
ERR.:Flashing
Q00J/Q00/Q01
CPU Status:Stop
Q00/Q01
Qn(H)
QnPH
QCPU
LCPU
RUN: Off
ERR.:Flashing
CPU Status:Stop
QnPRH
CPU
QnU
QnU
QnU