Mitsubishi Electric Q26UD(E)HCPU User Manual page 347

Melsecq series
Hide thumbs Also See for Q26UD(E)HCPU:
Table of Contents

Advertisement

Error
Error and cause
code
[BOOT ERROR]
The contents of the boot file are incorrect.
■Collateral information
2210
• Common information: Drive Name
• Individual information: -
■Diagnostic timing
• At power-on/At reset
[BOOT ERROR]
File formatting is failed at a boot.
■Collateral information
• Common information: Drive Name
2211
• Individual information: -
■Diagnostic timing
• At power-on/At reset
[BOOT ERROR]
The file was booted from the SD memory card to
the program memory or standard ROM but it was
not booted to the CPU module due to either of the
following reasons.
• The passwords for the password 32 do not
match between transfer source file and
destination file.
2213
• The password 32 is not configured for the
transfer source file while it is configured for the
destination file.
■Collateral information
• Common information: File name/Drive name
• Individual information: -
■Diagnostic timing
• At power-on/At reset
[BOOT ERROR]
The CPU module is locked.
■Collateral information
• Common information: -
2214
• Individual information: -
■Diagnostic timing
• At power-on/At reset
[RESTORE ERROR]
The device information (number of points) backed
up by the device data backup function is different
from that configured in "PLC Parameter".
Perform a restoration per power-on and reset until
the number of device points is identical to the
2220
value set in "PLC Parameter" or until the backup
data are deleted.
■Collateral information
• Common information: File name/Drive name
• Individual information: -
■Diagnostic timing
• At power-on/At reset
[RESTORE ERROR]
The device information backed up by the device
data backup function is incomplete. (The power
may have been off or the CPU module may have
been reset during performing the backup.)
Do not return the data when this error occurs.
2221
Also, delete the incomplete device information at
the time of this error occurrence.
■Collateral information
• Common information: File name/Drive name
• Individual information: -
■Diagnostic timing
• At power-on/At reset
Corrective action
Check the boot setting.
• Reboot.
• The cause is a hardware failure of the CPU
module. Please consult your local
Mitsubishi representative.
• Check the setting of the password 32 for
the transfer source file and destination files.
• Delete the boot setting from the parameter
file of the SD memory card.
When using the CPU module change function
with SD memory card, do not lock the CPU
module.
• Set the number of device points at the time
of backup to be identical to the device point
value set in "PLC Parameter". Then turn off
and on or reset the power supply.
• Delete the backed up data, turn the power
supply from off to on, and reset.
Reset the CPU module and run it again.
APPENDICES
LED status,
Corresponding
CPU status
CPU
Q00J/Q00/Q01
RUN: Off
Qn(H)
ERR.:Flashing
QnPH
QnPRH
CPU Status:Stop
QnU
LCPU
RUN: Off
Qn(H)
ERR.:Flashing
QnPRH
QnU
CPU Status:Stop
LCPU
RUN: Off
ERR.:Flashing
QnUDV
LCPU
CPU Status:Stop
RUN: Off
ERR.:Flashing
QnUDV
CPU Status:Stop
RUN: Off
ERR.:Flashing
QnU
LCPU
CPU Status:Stop
RUN: Off
ERR.:Flashing
QnU
LCPU
CPU Status:Stop
A