Error
Error and cause
code
[CAN'T EXECUTE(I)]
The IRET instruction exists before the FEND
instruction of the main routine program.
■Collateral information
• Common information: Program error location
• Individual information: -
■Diagnostic timing
• When instruction executed
[CAN'T EXECUTE(I)]
4223
• The IRET instruction was executed in the fixed
scan execution type program.
• The STOP instruction was executed in the fixed
scan execution type program.
■Collateral information
• Common information: Program error location
• Individual information: -
■Diagnostic timing
• When instruction executed
[CAN'T EXECUTE(I)]
The interrupt pointer for the module mounted on
the extension base unit is set in the redundant
system.
4225
■Collateral information
• Common information: -
• Individual information: -
■Diagnostic timing
• At power-on/At reset
[INST. FORMAT ERR.]
The number of CHK and CHKEND instructions is
not equal.
■Collateral information
4230
• Common information: Program error location
• Individual information: -
■Diagnostic timing
• When instruction executed
[INST. FORMAT ERR.]
The number of IX and IXEND instructions is not
equal.
■Collateral information
4231
• Common information: Program error location
• Individual information: -
■Diagnostic timing
• When instruction executed
[INST. FORMAT ERR.]
The configuration of the check conditions for the
CHK instruction is incorrect.
Alternatively, a CHK instruction has been used in a
low speed execution type program.
4235
■Collateral information
• Common information: Program error location
• Individual information: -
■Diagnostic timing
• When instruction executed
384
Corrective action
Read common information of the error using
the programming tool to identify the numeric
value (program error location). Check the
error step corresponding to the value, and
correct it as necessary.
Delete the setting of interrupt pointer for the
module mounted on the extension base unit,
since it cannot be used.
Read common information of the error using
the programming tool to identify the numeric
value (program error location). Check the
error step corresponding to the value, and
correct it as necessary.
Read common information of the error using
the programming tool to identify the numeric
value (program error location). Check the
error step corresponding to the value, and
correct it as necessary.
Read common information of the error using
the programming tool to identify the numeric
value (program error location). Check the
error step corresponding to the value, and
correct it as necessary.
LED status,
Corresponding
CPU status
QCPU
LCPU
RUN: Off
ERR.:Flashing
CPU Status:Stop
LCPU
RUN: Off
ERR.:Flashing
QnPRH
CPU Status:Stop
RUN: Off
ERR.:Flashing
Qn(H)
QnPH
CPU Status:Stop
RUN: Off
Qn(H)
ERR.:Flashing
QnPH
QnPRH
CPU Status:Stop
RUN: Off
ERR.:Flashing
Qn(H)
QnPH
CPU Status:Stop
CPU
QnU