Number
Name
Meaning
Error
Error
SD5 to
common
common
SD15
information
information
510
Explanation
*5
If a module is not mounted on any slots as set, FF
stored.
*6
If FFFF
is stored in SD6 (I/O No.), this indicates that
H
the I/O No. cannot be identified due to an error such as
overlap of an I/O No. in the I/O Assignment tab of "PLC
Parameter". In this case, identify the error location
using SD5. FFFF
is also stored in SD6 for the branch
H
module.
*11
The number found by dividing the start I/O number by
16 is stored.
2) File name/drive name
Number
Meaning
SD5
Drive
SD6
SD7
File name
SD8
(ASCII code: 8 characters)
SD9
SD10
7
Extension
2E
(.)
H
SD11
(ASCII code: 3 characters)
SD12
SD13
(Empty)
SD14
SD15
3) Time (value set)
Number
Meaning
SD5
Time : 1 s units (0 to 999 s)
SD6
Time : 1ms units (0 to 65535ms)
SD7
SD8
SD9
SD10
(Empty)
SD11
SD12
SD13
SD14
SD15
4) Program error location
Meaning
Number
SD5
File name
SD6
(ASCII code: 8 characters)
SD7
SD8
7
SD9
Extension
SD10
(ASCII code: 3 characters)
SD11
Pattern
SD12
Block No.
SD13
Step No./transition condition
Sequence step No. (L)
SD14
Sequence step No. (H)
SD15
*7
For extension names, refer to the table on Page 511,
Appendix 3 (1) (a).
*8
The description of the bit pattern is as follows:
15 14 to
4
3
2
1
0
(Bit number)
0 0
to
0
0
SFC block designation present (1)/absent (0)
(Not used)
SFC step designation present (1)/absent (0)
SFC transition designation present (1)/absent (0)
Set by
(When Set)
is
H
(Example) File name =
ABCDEFGH. IJK
b15 to b8 b7 to b0
42
(B) 41
(A)
H
H
44
(D) 43
(C)
H
H
46
(F)
45
(E)
H
H
48
(H) 47
(G)
H
H
49
(I)
2E
(.)
H
H
4B
(K) 4A
(J)
H
H
S (Error)
2E
(.)
H
8
Corresponding
Corresponding
ACPU
CPU
D9
QCPU
New
LCPU

Hide quick links: