Error
Error and cause
code
[FILE SET ERROR]
Program memory capacity was exceeded by
performing boot operation or automatic write to the
standard ROM.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• At power-on/At reset/At writing to programmable
controller
[FILE SET ERROR]
Program memory capacity was exceeded by
performing boot operation.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• At power-on/At reset
[FILE SET ERROR]
The file specified by parameters cannot be made.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• At power-on/At reset/At writing to programmable
controller/STOP  RUN
2401
[FILE SET ERROR]
• Although setting is made to use the device data
storage file, there is no empty capacity required
for creating the device data storage file in the
standard ROM.
• When the latch data backup function (to
standard ROM) is used, there is no empty
capacity required for storing backup data in
standard ROM. (The parameter number
" is displayed for the individual
"FFFF
H
information of the error.)
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• At power-on/At reset/At writing to programmable
controller/STOP  RUN
[FILE SET ERROR]
• Standard RAM capacity is insufficient that error
history of the module cannot be stored.
• Standard RAM capacity is insufficient that the
file register data cannot be stored.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• At power-on/At reset/At writing to programmable
controller/STOP  RUN
[FILE SET ERROR]
When the extended data register and extended
link register are configured in the File Register
Extended Setting in the Device tab of "PLC
Parameter", the size of the file register file is
2406
smaller than that specified in the PLC File tab.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• STOP  RUN
352
Corrective action
• Check and correct the parameters (boot
setting).
• Delete unnecessary files in the program
memory.
• Choose "Clear program memory" for boot
in the parameter so that boot is started after
the program memory is cleared.
• Check and correct the parameters (boot
setting).
• Delete unnecessary files in the program
memory.
• Choose "Clear program memory" for boot
in the parameter so that boot is started after
the program memory is cleared.
• Read the individual information of the error
using the programming tool to identify the
numeric value (parameter No.). Check the
drive name, file name, and size of the
parameter corresponding to the value, and
correct it as necessary.
• Format the drive.
• Delete unnecessary files on the drive to
increase free space.
Secure the empty capacity of the standard
ROM.
Secure sufficient space in the standard RAM.
• Correct the size for the file register file in
the PLC File tab of "PLC Parameter".
• Correct the setting for the "File Register
Extended Setting" in the Device tab of
"PLC Parameter".
LED status,
Corresponding
CPU status
Qn(H)
QnPH
QnPRH
RUN: Off
ERR.:Flashing
CPU Status:Stop
LCPU
RUN: Off
ERR.:Flashing
LCPU
CPU Status:Stop
CPU
QnU
QnU