Error
Error and cause
code
[BASE UNIT ERR.]
An error was detected in the LA1S extension base
unit.
■Collateral information
1760
• Common information: Module No. (Block No.)
• Individual information: -
■Diagnostic timing
• Always
*1
The operating status of the CPU module after an error has occurred can be set in parameter. (LED indication changes
according to the status.)
*2
The BAT.ALM LED turns on or flashes if the BATTERY ERROR occurs.
*3
The operating status of each intelligent function module after an error has occurred can be set in parameter (stop or
continue).
*4
Built-in Ethernet port QCPU and Built-in Ethernet port LCPU
*5
Universal model QCPU whose serial number (first five digits) is "13042" or later.
*6
This applies to the Q10UD(E)HCPU, Q13UD(E)HCPU, Q20UD(E)HCPU, Q26UD(E)HCPU, Q50UDEHCPU, and
Q100UDEHCPU.
*7
Modules whose serial number (first five digits) is "08032" or later When the CPU module is powered on or reset, the
error information is stored in SD6 (I/O No.).
Corrective action
Reset the CPU module and run it again. If the
same error code is displayed again, the
cause is a hardware failure of the LA1S
extension base unit. Please consult your local
Mitsubishi representative.