No.
Name
1)
POWER LED
2)
POWER LED
3)
+24V, 24G terminals
4)
FG terminals
5)
LG terminals
6)
Power input terminals
7)
Power input terminals
8)
Terminal screw
9)
Terminal cover
10)
Module fixing screw hole
● Do not wire to those terminals for which NC is stamped on the terminal block.
● Individually ground the LG and FG terminals with a ground resistance of 100  or less.
A1S62PN
10)
1)
9)
3)
4)
5)
6)
8)
On (green): Normal (5VDC output, momentary power failure within 20ms)
Off:
• AC power supply is on but the power supply module is out of order.
(5VDC error, overload, internal circuit failure, or fuse blown)
• AC power supply is not on
• Power failure (including an momentary power failure of 20ms or more)
On (green): Normal (5VDC output, momentary power failure within 10ms)
Off:
• DC power supply is on but the power supply module is out of order.
(5VDC error, overload, internal circuit failure, or fuse blown)
• DC power supply is not on.
• Power failure (including an momentary power failure of 10ms or more)
Used to supply 24VDC power to inside the output module (using external wiring).
Ground terminal connected to the shield pattern of the printed circuit board.
Grounding for the power supply filter. The potential of A1S61PN or A1S62PN terminal is 1/2 of
the input voltage.
Used to connect a 100VAC to 200VAC power supply.
Used to connect a 24VDC power supply.
M3.5 × 7 screw
Protective cover of the terminal block
Used to secure the module to the base unit.
(M4 screw, tightening torque : 0.66 to 0.89N•m)
CHAPTER 7 POWER SUPPLY MODULE