Mitsubishi Electric Q26UD(E)HCPU User Manual page 95

Melsecq series
Hide thumbs Also See for Q26UD(E)HCPU:
Table of Contents

Advertisement

Position of extension base unit
Q6B
Extension 1
Extension 2
Extension 1, Extension 2
Extension 3
Extension 1 to 3
Extension 4
Extension 1 to 4
Extension 5
Extension 1 to 5
Extension 6
The voltage supplied to the "IN" connector of the Q5B reaches 4.75 VDC or higher on the condition that the voltage drop (V)
at the extension cable between the main base unit and Q5B is 0.15 VDC or lower.
When connecting GOT by extension cable that is 13.2m or longer, the bus extension connector box A9GT-QCNB is
required.
Since the A9GT-QCNB is supplied with 5VDC from the power supply module loaded on the main base unit, 30mA must be
added to "Im" as the current consumption of the A9GT-QCNB.
For details of the method for GOT bus connection, refer to the following.
GOT-A900 Series User's Manual (Connection)
GOT1000 Series Connection Manual (Mitsubishi Products) for GT Works3
GOT2000 Series Connection Manual (Mitsubishi Products) For GT Works3 Version1
Number of bases
for GOT bus
Q5B
connection
Extension 3
Extension 4
Extension 5
Extension 6
Extension 7
CHAPTER 4 INSTALLATION AND WIRING
Voltage drop caused by extension cable from the
main base unit to the Q5B IN connector (V)
V=(R1+R2)(I1+Im)
V=(R1+R2+R3)(I2+Im)
V=(R1+R2+R3+R4)(I3+Im)
V=(R1+R2+R3+R4+R5)(I4+Im)
V=(R1+R2+R3+R4+R5+R6)(I5+Im)
4
93

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents