Mitsubishi Electric Q26UD(E)HCPU User Manual page 317

Melsecq series
Hide thumbs Also See for Q26UD(E)HCPU:
Table of Contents

Advertisement

Error
Error and cause
code
[TRK. CIR. ERROR]
• A tracking hardware fault was detected during
running.
• The tracking cable was disconnected and
reinserted without the standby system being
powered off or reset.
• The tracking cable is not secured by the
connector fixing screws.
1112
• The error occurred at a startup since the
redundant system startup procedure was not
followed.
■Collateral information
• Common information: -
• Individual information: -
■Diagnostic timing
• During running
[TRK. CIR. ERROR]
• A tracking hardware fault was detected during
running.
• The tracking cable was disconnected and
reinserted without the standby system being
powered off or reset.
• The tracking cable is not secured by the
connector fixing screws.
1113
• The error occurred at a startup since the
redundant system startup procedure was not
followed.
■Collateral information
• Common information: -
• Individual information: -
■Diagnostic timing
• During running
[TRK. CIR. ERROR]
A fault was detected by the initial check of the
tracking hardware.
■Collateral information
1115
• Common information: -
• Individual information: -
■Diagnostic timing
• At power-on/At reset
[TRK. CIR. ERROR]
• A tracking hardware fault was detected during
running.
• The tracking cable was disconnected and
reinserted without the standby system being
powered off or reset.
• The tracking cable is not secured by the
connector fixing screws.
1116
• The error occurred at a startup since the
redundant system startup procedure was not
followed.
■Collateral information
• Common information: -
• Individual information: -
■Diagnostic timing
• During running
[RAM ERROR]
The memory of the CPU module in the multiple
CPU high speed transmission area is faulty.
■Collateral information
1150
• Common information: -
• Individual information: -
■Diagnostic timing
• At power-on/At reset
Corrective action
• Check that the tracking cable is connected
and start up the module. If the same error
code is displayed again, the cause is a
hardware failure of the tracking cable or
CPU module. Please consult your local
Mitsubishi representative.
• Confirm the redundant system startup
procedure, and execute a startup again.
For details, refer to the QnPRHCPU User's
Manual (Redundant System).
• Check that the tracking cable is connected
and start up the module. If the same error
code is displayed again, the cause is a
hardware failure of the tracking cable or
CPU module. Please consult your local
Mitsubishi representative.
• Confirm the redundant system startup
procedure, and execute a startup again.
For details, refer to the QnPRHCPU User's
Manual (Redundant System).
The cause is a hardware failure of the CPU
module. Please consult your local Mitsubishi
representative.
• Check that the tracking cable is connected
and start up the module. If the same error
code is displayed again, the cause is a
hardware failure of the tracking cable or
CPU module. Please consult your local
Mitsubishi representative.
• Confirm the redundant system startup
procedure, and execute a startup again.
For details, refer to the QnPRHCPU User's
Manual (Redundant System).
• Take noise reduction measures.
• Reset the CPU module and run it again. If
the same error code is displayed again, the
cause is a hardware failure of the CPU
module. Please consult your local
Mitsubishi representative.
APPENDICES
LED status,
Corresponding
CPU status
CPU
RUN: Off
ERR.:Flashing
QnPRH
CPU Status:Stop
RUN: Off
ERR.:Flashing
QnPRH
CPU Status:Stop
RUN: Off
ERR.:Flashing
QnPRH
CPU Status:Stop
RUN: Off
ERR.:Flashing
QnPRH
CPU Status:Stop
RUN: Off
ERR.:Flashing
QnU
CPU Status:Stop
A
315