Mitsubishi Electric Q26UD(E)HCPU User Manual page 47

Melsecq series
Hide thumbs Also See for Q26UD(E)HCPU:
Table of Contents

Advertisement

(7) Precautions when using AnS/A series modules
1) When using the AnS series special function modules shown below, a limitation is placed on an accessible
device range.
• A1SJ71J92-S3 type JEMANET interface module
• A1SD51S type intelligent communication module
Device
Input (X), Output (Y)
Internal relay (M), Latch relay (L)
Link relay (B)
Timer (T)
Counter (C)
Data register (D)
Link register (W)
Annunciator (F)
2) The modules listed below cannot be used.
Product
MELSECNET/10 network module
MELSECNET(II), /B data link module
Ethernet module
Serial communication module, computer link module
Computer link/multidrop link module
CC-Link system master/local module
ME-NET interface module
*1
Only multidrop link function can be used. The computer link function and printer function cannot be used.
3) The AnS/A series dedicated instructions for the following modules cannot be used.
Rewriting using the FROM or TO instruction is required.
Product
High speed counter module
MELSECNET/MINI-S3
Positioning module
ID module
CHAPTER 2 SYSTEM CONFIGURATION
Accessible device range
X/Y0 to 7FF
M/L0 to 8191
B0 to FFF
T0 to 2047
C0 to 1023
D0 to 6143
W0 to FFF
F0 to 2047
Model
A1SJ71LP21, A1SJ71BR11, A1SJ71LR21, A1SJ71QLP21,
A1SJ71QLP21S, A1SJ71QBR11, A1SJ71QLR21
A1SJ71AP21, A1SJ71AR21, A1SJ71AT21B
A1SJ71E71N-T, A1SJ71E71N3-T, A1SJ71E71N-B2(-B5),
A1SJ71QE71N-T, A1SJ71QE71N3-T, A1SJ71QE71N-B2(-B5)
A1SJ71UC24-R2(-PRF), A1SJ71QC24(-R2), A1SJ71QC24N(-R2),
A1SJ71QC24N1(-R2)
*1
A1SJ71UC24-R4
A1SJ61BT11, A1SJ61QBT11
A1SJ71ME81
Model
A1SD61, A1SD62, A1SD62D(-S1), A1SD62E
A1SJ71PT32-S3, A1SJ71T32-S3
A1SD75P1-S3(P2-S3/P3-S3)
A1SJ71ID1-R4, A1SJ71ID2-R4
2
45