Mitsubishi Electric Q26UD(E)HCPU User Manual page 450

Melsecq series
Hide thumbs Also See for Q26UD(E)HCPU:
Table of Contents

Advertisement

Error code
Error item
(Hexadecimal)
E-mail related
C124
H
error
E-mail related
C126
H
error
E-mail related
C13D
H
error
E-mail related
C13E
H
error
E-mail related
C140
H
error
E-mail related
C141
H
error
E-mail related
C144
H
error
E-mail related
C146
H
error
E-mail related
C151
H
error
E-mail related
C152
H
error
E-mail related
C170
H
error
E-mail related
C1B6
H
error
Predefined
C400
protocol related
H
error (Ethernet)
Predefined
C401
protocol related
H
error (Ethernet)
Predefined
C402
protocol related
H
error (Ethernet)
Predefined
C404
protocol related
H
error (Ethernet)
448
Error details
The response from the SMTP server timed out.
(SMTP state transition timeout error)
Connection to the SMTP server cannot be
closed. (Failed-to-close-connection error)
SMTP server authentication error
SMTP server authentication unsupported error
Connection to the POP3 server cannot be
opened. (TCP connection timeout error)
The CPU module cannot communicate with the
POP3 server. (Error response) (TCP connection
error)
The CPU module was not able to receive a
response from the POP3 server. (POP3 state
transition timeout error)
Connection to the POP3 server cannot be
closed. (Failed-to-close-connection error)
The e-mail address set to the CPU module in E-
mail Setting parameter differs from the account
name set to the mailbox on the server side.
(User mailbox specification error)
The password set to the CPU module in E-mail
Setting parameter differs from the one set on the
server side. (Password setting error)
An error is returned from the DNS server.
The destination number setting is incorrect.
(Destination number setting error)
• SP.ECPRTCL instruction was executed before
the Predefined protocol ready (SM1354) is
turned ON.
• SP.ECPRTCL instruction was executed while
error occurred in the protocol setting data.
Executed protocol No. has not been registered.
Protocol setting data is invalid.
SP.ECPRTCL instruction ended abnormally
because the cancel request was accepted during
protocol execution.
Corrective action
• Check that the SMTP server is operating
correctly.
• Check that there is no load on the network.
• Check that the SMTP server is operating
correctly.
• Check that there is no load on the network.
• Check that the account name and password of
the SMTP server are correctly set.
• Check the operating status of the SMTP server.
• Check that the SMTP server supports SMTP
Authentication.
• Change the authentication setting in parameter.
(Deselect the "Authenticate" checkbox, or select
"Use POP before SMTP").
• Check the port number of the POP3 server.
• Check that the communications with the POP3
server is enabled by using the PING command.
Check that the POP3 server is not busy.
• Check that the POP3 server is operating
correctly.
• Check that there is no load on the network.
• Check that the POP3 server is operating
correctly.
• Check that there is no load on the network.
Correct the e-mail address set to the CPU module
so that the account name matches the one set to
the server.
Correct the password set to the CPU module so
that it matches the one set to the server.
• Check that the IP address of the DNS server is
set correctly.
• Check that the mail server name (SMTP server
name, POP server name) is set correctly.
• Check with a network manager if the server set
as a DNS server is operating correctly.
• Check and correct the destination number
setting.
• Check and correct the e-mail address setting in
parameter or e-mail address table.
• Execute the SP.ECPRTCL instruction after the
Predefined protocol ready (SM1354) is turned
ON.
• Execute the SP.ECPRTCL instruction after
rewriting protocol setting data to CPU.
• If the same error code is displayed again after
rewriting, the cause is a hardware failure of the
CPU module. Please consult your local
Mitsubishi representative.
• Execute the protocol again after checking the
specified protocol No.
• Register the corresponding protocol to the
specified protocol No.
Check the protocol setting data and register it
again.
Check the canceled protocol in SP.ECPRTCL
instruction control data (number of executions) and
remove the cause of cancel operation.
Corresponding
CPU
LCPU
LCPU
LCPU
LCPU
LCPU
LCPU
LCPU
LCPU
LCPU
LCPU
LCPU
LCPU
QnUDV
LCPU
QnUDV
LCPU
QnUDV
LCPU
QnUDV
LCPU

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents