Mitsubishi Electric Q26UD(E)HCPU User Manual page 133

Melsecq series
Hide thumbs Also See for Q26UD(E)HCPU:
Table of Contents

Advertisement

No.
Name
1)
Base unit installation hole
2)
Cover
3)
Extension cable connector
4)
POWER LED
5)
MODE LED
6)
RUN LED
7)
ERR. LED
8)
USER LED
9)
BAT. LED
10)
Serial number display
11)
Module connector
12)
DIN rail adopter mounting holes
13)
FG terminal
14)
LG terminal
15)
Power input terminals
16)
Battery
Pear-shaped hole for installing the unit on a panel such as a control panel. (For M4 screw)
Protective cover for extension cable connector. Remove this cover when connecting an
extension base unit.
Connector for transferring signals to or from the extension base unit. Connect an extension
cable.
Power indicator LED for 5VDC. Turns on in green during normal output of 5VDC.
Indicates the mode of the CPU module.
On: Q mode
Flash:
Executional conditioned device test is being executed.
External input/output forced on/off function is being executed.
Indicates the operating status of the CPU module.
On: During operation with the RUN/STOP/RESET switch set to "RUN"
Off: During stop with the RUN/STOP/RESET switch set to "STOP"
When the error that stops operation is detected.
Flash:
When parameters or a program is written during STOP and the RUN/STOP/RESET
switch is moved from "STOP" to "RUN".
To turn on the RUN LED after writing the program, perform the following operations.
• Shift the RUN/STOP/RESET switch from "RUN" to "STOP" to "RUN".
• Perform reset with the RUN/STOP/RESET switch.
• Power on the programmable controller again.
To turn on the RUN LED after writing the parameters, perform the following operations.
• Perform reset with the RUN/STOP/RESET switch.
• Power on the programmable controller again.
(If the RUN/STOP/RESET switch is shifted from "RUN" to "STOP" to "RUN"
after changing the parameter values, the new values are not reflected on the parameters
related to the intelligent function module, such as the network parameters.)
On: When the self-diagnostic error (other than a battery error) that will not stop operation is
detected.
(When continuation of operation at error detection is set in the parameter)
Off: Normal
Flash:
When the error that stops operation is detected.
When reset operation is performed with the RUN/STOP/RESET switch.
On: Annunciator (F) turned on.
Off: Normal
Flash (yellow): Battery error due to voltage drop of the CPU module battery.
On (green):
Keeps on for 5 seconds after competing of restoring the data that are backed up by the
latch data backup function to the standard ROM.
Flash (green):
When data are backed up to the standard ROM by the latch data backup function
Off: Normal
Shows the serial number printed on the rating plate.
Connector used for mounting an module or intelligent function module.
(To the connector of the spare space where no module is mounted, fit the accessory connector
cover or the blank cover module (QG60) to prevent dust from entering.)
Holes for mounting a DIN rail adaptor.
Ground terminal connected with the shield pattern of the printed circuit board.
Power filter ground having a half potential of the input voltage.
Power input terminals for connection of a 100VAC to 200VAC power supply.
Backup battery for use of the standard RAM and battery power time function.
CHAPTER 6 CPU MODULE
Application
6
131